DIP Switch Programming

Table 4-1 lists the programming DIP switches, and describes what each of their settings
accomplish.
DIP
Function
Switch
1
SW1
Initial Message
off
Delay
on
off
on
off
on
off
on
Delay Between
Messages
Message
Repeat
151267
Table 4-1: DIP Switch Programming
Switch Number
2
3
4
5
6
off
off
off
off
on
off
on
off
off
on
off
on
on
on
on
on
off
off
on
off
off
on
on
on
off
on
off
on
off
on
off
on
firealarmresources.com
Setting
7
8
0 Seconds
4 Seconds
8 Seconds
12 Seconds
16 Seconds
20 Seconds
24 Seconds
28 seconds
4 Seconds
8 Seconds
12 Seconds
16 Seconds
off
off
None
off
off
1
on
off
2
on
off
3
off
on
4
off
on
5
on
on
6
on
on
Continuously
Comments
This option selects the
initial delay before the
message starts playing
after an alarm. The
tone sounds during the
delay.
For UL 864
installations, this
option must be set to a
minimum of 8 seconds.
This option selects the
amount of time
between messages.
This option selects the
total number of times
that the message will
be repeated.
For UL 864
installations, this
option must be set to a
minimum of 3.