6 Troubleshooting
Troubleshooting by protection code (Outdoor unit)
P116
Protection 
code
•  Outdoor unit LED301 blinks 16 times.
•  This protection code is displayed continuously until the abnormal situation ends, without leading to an alarm.
LD301 blinks 16 times.
High load stop
79
SMGB0135 rev.0 - 06/2020
* This is not a failure in case that 
operation continues after restarting.
Compressor stopped since current exceeded 
the threshold value due to high load. It
restarts after a fixed time (3 minutes).*
Is the heat exchanger of the outdoor unit clogged 
or are its surroundings blocked by something?
Is there any abnormality in the refrigerating cycle?
Software Ip cut stop
Yes
Remove the cause of the 
problem.
No
Yes
Fix the point of abnormality.
No
No
Is the service valve open?
Yes
Abnormal
Check the compressor 
for loose connectors and 
continuity of the cord.
Normal
Is a leakage breaker
installed?
No
Abnormal
Is the insulation of the compressor 
normal? Check it with a megger.
Normal
Conduct a "self-check".
Open the service valve.
Fix the point of 
abnormality.
Replace the compressor and 
inspect the outdoor electrical
parts.
Replace the parts found to be 
defective based on the results of 
the "self-check" evaluation.