6 Troubleshooting
Outdoor unit

Outdoor fan motor check diagnosis method
1 Put the power off.
2 Remove the outdoor fan motor's connector from CN24.
3 Rotate the fan motor by hand and check whether the fan motor is locked or not.
4 Measure the resistance between each terminal of the fan motor connector. Normal resistance between each terminal: 
60 ~ 100 Ω
5 Insert the fan motor's connector.