6 Troubleshooting
Outdoor unit
No
Yes
LD301 blinks 10 times.
Power supply voltage error
No
Yes
LD301 blinks 7 times.
Thermistor abnormality
No
Yes
LD301 blinks 6 times.
Increase of compressor 
temperature
No
Yes
LD301 blinks 16 times
High load stop
No
Yes
LD301 blinks 5 times.
Operation stopped
due to heavy load of 
Exceeded the lower limit of 
the compressor.
overload
No
Yes
LD301 blinks 4 times
This is a failure in starting up the 
compressor. Check the compressor 
connectors for looseness and continuity.
Switchover failure
No
Yes
Operation stopped due to the detection of 
LD301 blinks 3 times.
abnormality by the compressor control. It 
may be an abnormality of the drive circuit 
Abnormally slow rotation
in case of heavy load.
No
Yes
Operation stopped due to the detection of 
LD301 blinks twice
abnormality by the compressor control. It may be an 
abnormality of the compressor and an abnormality of 
Peak current cut
the drive circuit in case of heavy load.
65
SMGB0135 rev.0 - 06/2020
AC voltage lower than 187 V or greater than 253 V
Is there a voltage of AC 220-230 V 
between terminal boards L and N?
AC voltage between 187 and 253 V
Is DC voltage between 264 and 358 V? Refer to 
the label on the cover of the electrical parts for the 
measuring points.
Normal
Check for loose or poorly inserted thermistors.
Normal
Check the thermistors for wire breaks and short-circuits.
Normal
An increase of compressor 
Check whether the OH thermistor is loose or poorly inserted.
temperature has been 
detected by the OH 
thermistor.
Check the OH thermistor for wire breaks and short-circuits
Normal
* This is not a failure in case that 
operation continues after restarting.
Compressor stopped since current exceeded 
the threshold value due to high load. It
restarts after a fixed time (3 minutes).*
Is the heat exchanger of the outdoor unit clogged 
or are its surroundings blocked by something?
Is there any abnormality in the refrigerating cycle?
Abnormal
Check for 
loose or poorly 
inserted reactor.
Abnormal
Abnormal
Abnormal
Normal
Abnormal
Inspect the refrigerating cycle. 
(It may be due to a cause such 
as refrigerant leakage)
Yes
Remove the cause of the 
problem.
No
Yes
Fix the point of abnormality.
No
No
Is the service valve open?
Yes
Abnormal
Check the compressor 
for loose connectors and 
continuity of the cord.
Normal
Is a leakage breaker
installed?
No
Abnormal
Is the insulation of the compressor 
normal? Check it with a megger.
Normal
Conduct a "self-check"
Check the power supply.
Check the connection of the 
reactor wire. If it is OK, please 
replace the reactor.
Replace the outdoor electrical
parts (due to circuit abnormality).
Replace the outdoor electrical
parts (due to abnormality in the 
voltage detection circuit).
Fix the connection of the 
thermistors.
Replace any abnormal 
thermistors.
Replace the outdoor electrical
parts (due to abnormality in the 
thermistor detection circuit).
Fix the connection of the 
OH thermistor.
Replace the OH thermistor.
In case that inspecting the refrigerating cycle 
does not help to solve the problem, replace 
the outdoor electrical parts (due to abnormality 
in the thermistor detection circuit).
Open the service valve
Fix the point of 
abnormality.
Replace the compressor and 
inspect the outdoor electrical
parts.
Replace the parts found to be 
defective based on the results of 
the "self-check" evaluation.
6