6 Troubleshooting
Indoor unit
71
Alarm code
•  The alarm code is displayed on the LCD controller when the temperature of the water is higher than 86 °C.
•  This alarm forces the heat pump and the heater to stop.
•  The unit should be stopped to release the alarm.
Is the
Check and restart
No
the thermostat 
heater
working?
reset switch
Yes
Disconnect CN15
Relay-AR from
the PCB
Is the
Yes
Check relay-AR 
heater still
continuity
working?
No
80
Alarm code
•  The alarm code is displayed on the unit controller when there is no communication between indoor unit PCB and the 
unit controller for 90 seconds.
•  This alarm forces all operations to stop.
•  The unit should be stopped to release the alarm.
Are the connections
between PCB and 
LCD controller correctly 
Controller
Faulty Unit controller or PCB
73
SMGB0135 rev.0 - 06/2020
Is the
heater
working?
Yes
Is there
No
continuity to 
the heater
thermostat?
Yes
Faulty realy-AR
(Change it)
Communication failure between Indoor unit and LCD controller (PC-ARFTE)
connected?
Unit
PCB
CN2-1
CN20-1
CN2-2
CN20-2
CN2-3
CN20-3
CN2-4
CN20-4
Yes
(Check it)
Tank over-temperature limit protection
No
Disconnect
wires and check
heater continuity
Faulty PCB
(Change it)
No
Check wiring: repair broken / wrong wiring
Contact your local dealer
No
Is there
Faulty heater
continuity?
(Change it)