6 Troubleshooting
Outdoor unit
6.1 Outdoor unit
6.1.1 Discharge procedure and power shut off method for power circuit
!
D A N G E R
Voltage of about 350 V is charged between the terminal of smoothing capacitors.
During continuity check for each circuit part of the outdoor unit, be sure to discharge the smoothing capacitors.
Discharge Procedure
1 Turn off the power.
2 After power is turned off, wait for 10 minutes or more. Then, remove electrical parts cover and apply soldering iron of
30 to 75 W for 15 seconds or more to IPM(24 ) and IPM (20) terminals on the main PCB as shown in the figure below,
in order to discharge voltage in smoothing capacitor.
Lead wire
58
SMGB0135 rev.0 - 06/2020
Do not use a soldering iron with transformer:
Otherwise, thermal fuse inside transformer will
be blown.
SOLDERING IRON (30 TO 75W)