B.7: Panel Circuits - Honeywell NOTIFIER APS2-6R/E Instruction Manual

Table of Contents

Advertisement

Panel Circuits
8. Attach battery interconnect cable.
B.7 Panel Circuits
All four (4) NACs (Notification Appliance Circuits) on the ICM and all four (4) on the ICE are powered from TB2
on the APS2-6R. The NACs share the total 6A available from that circuit. Auxiliary power harness (P/N 71091)
needs to have the header cut off and wired to the terminal block.
APS2-6R/E Instruction Manual — P/N 53232:B 2/26/2014
Spkr4
TRBL
SPKR4
Riser TRBL
Phone 1
Phone1 TRBL
PHONE
1 AND 2
Phone 2
2 X 2W
1 X 4W
Phone 2 TRBL
TB9
Phone 3
PHONE
3 AND 4
Phone 3 TRBL
2 X 2W
CHGTRBL
1 X 4W
Phone 4
BATTRBL
Phone 4 TRBL
XPIQ-PS Power
A.C.Fail
Non-power-limited
+
AC
GND NEUT HOT
POWER FOR XPIQ-MB
Figure B.7 Wiring to XPIQ
Note: Maintain 0.25" spacing between
Power-limited and Non-power-limited
wiring. Install tie wraps and adhesive
squares to secure the wiring.
Non-power-limited
APS2-6R
Figure B.8 Wiring to an ICM/ICE Module
Note: Maintain 0.25" spacing between
Power-limited and Non-power-limited
wiring. Install tie wraps and adhesive
squares to secure the wiring.
XPIQ-MB
XPIQ-PS Control Cable
APS2-6R
+
+
+ to battery
- back-up
CONTROL
+ BATTERY -
J2
INTERFACE
J1
F2
Non-power-limited
XPIQ-PS
ICM
blue
black
Power-limited
Auxiliary power harness
(P/N 71091)- cut off
header and attach to TB2
UL 864 8th Edition Configurations
EXT TRBL IN
J
5 J
6
J
5 J
6
ICE
blue
black
27

Advertisement

Table of Contents
loading

Table of Contents