UL 864 8th Edition Configurations
7. Attach battery interconnect cable.
B.6 XPIQ Transponder
The APS2-6R must be mounted to the CHS-4/L chassis in the CAB-3/4 Series backbox. See "In a CAB-3/4 Series
Backbox" on page 11.
B.6.1 Connecting to the XPIQ-MB and XPIQ-PS
1. Connect trouble output from J3 on the APS2-6R to J9 on the XPIQ.
2. Place shunt across both pins of JP4 on the APS2-6R.
3. Connect cable P/N 75121 from J9 on the APS2-6R to TB9 on the XPIQ-MB to supply non-power-limited
power. See the XPIQ Instruction Manual for information.
4. Connect primary power from TB1 on the APS2-6R to TB1 on the XPIQ-PS.
5. Connect AC power to TB1 on the XPIQ-PS. Make sure to properly ground the unit to the backbox.
6. Connect batteries to TB2 on the XPIQ-PS.
7. Connect secondary power from TB3 on the APS2-6R to TB2 on the XPIQ-PS.
26
Note: Maintain 0.25" spacing between
Power-limited and Non-power-limited
wiring. Install tie wraps and adhesive
squares to secure the wiring.
Non-power-limited
to battery +
back-up -
AMPS-24
Figure B.6 Wiring to AMPS-24 and CPU-3030
WARNING:
!
Be sure to finish installation before applying power. Test AC power before continuing.
Power-limited
APS2-6R
Non-power-limited
APS2-6R/E Instruction Manual — P/N 53232:B 2/26/2014
XPIQ Transponder
CPU-3030