7. Attach battery interconnect cable.
B.2 AFP-300/AFP-400
The APS2-6R must be mounted to the CHS-4/L chassis in the CAB-3/4 Series backbox. See "In a CAB-3/4 Series
Backbox" on page 11.
B.2.1 Connecting to the MPS-400 Power Supply
1. Connect trouble output from J3 on the AP2S-6R to J4 on the MPS-400.
2. Place shunt across both pins of JP4 on the APS2-6R.
3. Connect primary power from TB1 on the APS2-6R to terminal block TB1 (
4. Connect AC power to TB1 on the MPS-400. Make sure to properly ground the unit to the backbox.
5. Connect batteries to TB1 on the MPS-400
6. Connect secondary power from TB3 on the APS2-6R to terminal block TB1 (+ and -) on the MPS-400.
APS2-6R/E Instruction Manual — P/N 53232:B 2/26/2014
Note: Maintain 0.25" spacing between
Power-limited and Non-power-limited
wiring. Install tie wraps and adhesive
squares to secure the wiring.
grounding
stud
JP2
AC
Non-power-limited circuits
The shaded area and dotted lines represent
the APS2-6R and wiring behind the panel.
BB-17 Backbox
with batteries
Figure B.1 Wiring to AFP-200
WARNING:
!
Be sure to finish installation before applying power. Test AC power before continuing.
Power-limited circuit