UL 864 8th Edition Configurations
7. Attach battery interconnect cable.
B.4 NFS-640
The APS2-6R must be mounted to the CHS-4/L chassis in the CAB-3/4 Series backbox. See "In a CAB-3/4 Series
Backbox" on page 11.
B.4.1 Connecting to a CPU-640
1. Connect trouble output from J3 on the APS2-6R to J11 on the CPU-640.
2. Place shunt across both pins of JP4 on the APS2-6R.
3. Connect primary power from TB1 on the APS2-6R to TB2 on the CPU-640.
4. Connect AC Power to TB2 on the CPU-640. Make sure to properly ground the unit to the backbox.
5. Connect batteries to TB1 on the CPU-640.
6. Connect secondary power from TB3 on the APS2-6R to TB1 on the CPU-640.
24
Note: Maintain 0.25" spacing between
Power-limited and Non-power-limited
wiring. Install tie wraps and adhesive
squares to secure the wiring.
Non-power-limited
to battery +
back-up -
Non-power-limited
Figure B.4 Wiring to MPS-24B
WARNING:
!
Be sure to finish installation before applying power. Test AC power before continuing.
MPS-24B
APS2-6R
APS2-6R/E Instruction Manual — P/N 53232:B 2/26/2014
NFS-640