Honeywell NOTIFIER FCPS-24S6 Installation Manual

Honeywell NOTIFIER FCPS-24S6 Installation Manual

Field charger/power supply
Table of Contents

Advertisement

Field Charger/Power Supply
FCPS-24S6 & FCPS-24S8
FCPS-24S6E & FCPS-24S8E
FCPS-24S6C & FCPS-24S8C
Installation Manual
Document 51977
J2
7/11/2014
Rev:
P/N 51977:J2
ECN 14-570

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell NOTIFIER FCPS-24S6

  • Page 1 Field Charger/Power Supply FCPS-24S6 & FCPS-24S8 FCPS-24S6E & FCPS-24S8E FCPS-24S6C & FCPS-24S8C Installation Manual Document 51977 7/11/2014 Rev: P/N 51977:J2 ECN 14-570...
  • Page 2 Fire Alarm & Emergency Communication System Limitations While a life safety system may lower insurance rates, it is not a substitute for life and property insurance! An automatic fire alarm system—typically made up of smoke (caused by escaping gas, improper storage of flammable materi- detectors, heat detectors, manual pull stations, audible warning als, etc.).
  • Page 3 HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
  • Page 4 •Brief description of content you think should be improved or corrected •Your suggestion for how to correct/improve documentation Send email messages to: FireSystems.TechPubs@honeywell.com Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
  • Page 5: Table Of Contents

    Table of Contents Section 1: System Overview ....................8 1.1: General................................8 1.2: Features................................8 1.3: Start-up Procedure ............................9 1.4: Jumpers ................................10 1.4.1: Jumper JP1 - Ground Fault Detection ....................10 1.4.2: Jumpers JP2 and JP3: Coded/Noncoded Input Selection ..............10 1.5: LED Indicators.............................10 1.6: Specifications...............................10 1.7: General.................................13 Section 2: Installation......................
  • Page 6 Table of Contents Appendix A: Wire Requirements................... 43 Index ............................44 FCPS-24S Series Instruction Manual — P/N 51977:J2 7/11/2014...
  • Page 7 It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies: • Underwriters Laboratories Standards • NFPA 72 National Fire Alarm Code Before proceeding, the installer should be familiar with the following documents. NFPA Standards NFPA 72 National Fire Alarm Code NFPA 70 National Electrical Code...
  • Page 8: Section 1: System Overview

    Section 1: System Overview The FCPS-24S6 is a 6 amp power supply and the FCPS-24S8 is an 8 amp power supply. Each FCPS-24S power supply is a compact, cost-effective, remote power supply and battery charger which provides ADA compatible strobe synchronization. Each remote power supply consists of a filtered 24 VDC output that can be configured to drive four Style Y (Class B) NACs (Notification Appliance Circuits).
  • Page 9: Start-Up Procedure

    Start-up Procedure System Overview • Maximum current available for any one output circuit: 3.0 amps special application, 300mA regulated • Maximum total continuous current available: – 4.0 amps for FCPS-24S6 – 6.0 amps for FCPS-24S8 • Maximum total short term current (one hour maximum): –...
  • Page 10: Jumpers

    System Overview Jumpers 1.4 Jumpers CAUTION: DISCONNECT POWER REMOVE ALL POWER (AC & DC) BEFORE CUTTING OR MOVING ANY JUMPERS. 1.4.1 Jumper JP1 - Ground Fault Detection The Ground Detection circuit monitors for zero impedance between the power supply and ground. Jumper JP1 is located in the top right section of the power supply circuit board.
  • Page 11 Specifications System Overview Control Input Circuits - TB4, Terminals 3 (+) & 4 (-) and 7 (+) & 8 (-) • Trigger Input Voltage: 9 to 32 VDC • Input Current Draw in Alarm Polarity: – 16 to 32 volts, 16.0 mA maximum per input –...
  • Page 12 System Overview Specifications Power-limited (Class 2), Supervised, Special Application or Regulated Nonpower-limited To Transformer #1 NAC/Out 1 + To Transformer #2 NAC/Out 1 - Trouble Relay NAC/Out 2 + Form-C Fail-safe Supervised, NAC/Out 2 - Nonsupervised Nonpower-limited NAC/Out 3 + (shown energized) Earth NAC/Out 3 -...
  • Page 13: General

    General System Overview 1.7 General The FCPS may be used in a number of different applications. It may be used as a remotely- mounted power supply and battery charger where it can provide up to four coded or noncoded, syn- chronized or nonsynchronized NACs (Notification Appliance Circuits).
  • Page 14: Section 2: Installation

    Section 2: Installation Carefully unpack the system and check for shipping damage. Select a location for the cabinet that is in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the power supply. With the hinge mounting on the left, determine the number of conductors required for the devices to be installed and determine the appropriate knockouts.
  • Page 15 Backbox Mounting Installation 2.875” (7.3 cm) Depth = 3.050” (7.75 cm) Backbox = 14.5” (36.8 cm) 0.75” (1.9 cm) 2.7” (6.86cm) 9.1” (23.1 cm) Ground Stud 10.625” (26.99 cm) Height=15.00” Mounting Plate Pem Studs (38.10 cm) Backbox Mounting Holes Bottom 1.125”...
  • Page 16: Nac Circuit Wiring

    Installation NAC Circuit Wiring 2.2 NAC Circuit Wiring 2.2.1 Style Y (Class B) The standard configuration for NACs is Style Y (Class B) as shown in Figure 2.3. 4.7K: ELR Horn Strobe Alarm Polarity Shown Horn Strobe Horn Strobe FCPS-24S Circuit Board Figure 2.3 NAC Style Y (Class B) 2.2.2 ZNAC-4 Class A Option Module The ZNAC-4 is an optional Class A conversion module which mounts to connector J3 on the upper...
  • Page 17: Addressable Module Mounting

    Addressable Module Mounting Installation 2.3 Addressable Module Mounting The FCPS-24S has been designed to allow the mounting of an addressable control, relay or monitor module on the main circuit board inside the power supply cabinet with the module status LED visi- ble through the closed door.
  • Page 18 Installation NEC Power-limited (Class 2) Wiring Requirements AC Power Output Circuits Relay Contacts Nonpower-limited Power-limited Circuits (Class 2) Nonpower-limited Circuit Input Circuits Power-limited Circuit (Class 2) Specific Application Power & SLC are Power-limited Circuits (Class 2) *If the SLC device does not match the one in this figure, refer to the SLC manual wiring conver-...
  • Page 19 Notes FCPS-24S Series Instruction Manual — P/N 51977:J2 7/11/2014...
  • Page 20: Section 3: Programming Options

    Section 3: Programming Options This section describes the programming options available via DIP switch settings. The FCPS can be field programmed using option DIP switch SW1 which is located in the lower center of the cir- cuit board. Refer to the following illustration for switch location and DIP switch placement in the ON and OFF positions.
  • Page 21: Dip Switch Settings

    DIP Switch Settings Programming Options 3.1 DIP Switch Settings The following table lists the FCPS programmable features and the switch settings required to select a particular feature. A detailed description of each feature is presented in the following pages. SW1 DIP Switch This switch works in conjunction with switch 2 to determine the Strobe Synchronization Type 1 OFF, 2 OFF = no sync (steady +24V) - default 1 OFF, 2 ON = System Sensor...
  • Page 22: Programmable Features Description

    Programming Options Programmable Features Description 3.2 Programmable Features Description 3.2.1 Synchronization Type Selection Synchronization is a feature that controls the activation of notification appliances in such a way that all devices will turn on and off at exactly the same time. This is particularly critical when activat- ing strobes which must be synchronized to avoid random activation and a potential hazard or con- fusion.
  • Page 23: 3: Ac Fail Delay/Aux. Trouble Relay Function

    Programmable Features Description Programming Options vide synchronization timing pulses from a dedicated sync output connector. Connect the FCPS sync input terminals to the FACP sync output connector instead of the FACP NAC. Note that the Synchronization Type configured by DIP switches 1 and 2 must be set to the same type as the signal being fed to the Sync Input circuit in the event that Selective Silence is employed.
  • Page 24: Auxiliary Power Control

    Programming Options Programmable Features Description Split Temporal • FCPS configured as Master (switch 3 OFF), Control Input #1 controls NAC Outputs 1 & 2 and Control Input #2 controls Outputs 3 & 4 which will generate a Temporal code signal without sync;...
  • Page 25 Notes FCPS-24S Series Instruction Manual — P/N 51977:J2 7/11/2014...
  • Page 26: Section 4: Trouble Supervision

    Section 4: Trouble Supervision 4.1 Supervision via FACP Notification Appliance Circuit 4.1.1 Supervision of FACP to FCPS wiring The FACP (Fire Alarm Control Panel) supervises the connection between itself and the FCPS-24S via the control panels NAC End-of-Line Resistor (ELR). The ELR must be installed at the FCPS end of the circuit, after the last notification appliance on the circuit.
  • Page 27: Ac Loss Reporting Delay

    AC Loss Reporting Delay Trouble Supervision • With SW1 switch 4 set to the ON position, AC Fail/brownout reporting will be delayed 2 hours and the following trouble conditions will cause the normally energized Aux. Trouble Relay to change states regardless of whether the panel is in alarm or standby: –...
  • Page 28: Section 5: Applications

    Section 5: Applications 5.1 Controlling Four NACs With One Input and Selective Silence NOTE: The Relay Module is required only for this application with the power supply set as Master. If the power supply is set as Slave, the Relay Module is not required. In Slave mode, selective silence (horn mute) is provided by the FACP through the sync input.
  • Page 29 Controlling Four NACs With One Input and Selective Silence Applications The control module is shown to demonstrate the use of a remotely mounted device associated with an addressable fire alarm control panel. The module could be replaced with any circuit capable of polarity reversal, such as an FACP NAC.
  • Page 30: Controlling Three Nacs And One Door Holder With One Input

    Applications Controlling Three NACs and One Door Holder With One Input Supervise the power wiring between the FCPS-24S auxiliary 24 VDC output on TB4, Terminals 9 & 10 with an EOL relay (P/N: EOLR-1). For a list of compatible devices, refer to the Notifier Device Compatibility Document #15378. IMPORTANT! When the power supply is programmed for both Selective Silence and Slave Mode, TB4 Terminal 7 (IN+) must be jumpered to Terminal 9 (AUX+) and Terminal 8 (IN-) must be jumpered to Terminal 10 (AUX-).
  • Page 31 Controlling Three NACs and One Door Holder With One Input Applications The control module is shown to demonstrate the use of a remotely mounted device associated with an addressable fire alarm control panel. The module could be replaced with any circuit capable of polarity reversal, such as an FACP Notification Appliance Circuit.
  • Page 32: Split Temporal Mode Of Operation

    Applications Split Temporal Mode of Operation 5.3 Split Temporal Mode of Operation In this application, the power supply has been set as a master with two synchronized and two non- synchronized outputs as determined by the Split Temporal mode feature. Control Input #1 (TB4, Terminals 3 &...
  • Page 33: Remote Supply With Resettable And Nonresettable Power

    Remote Supply With Resettable and Nonresettable Power Applications The following notes apply to Figure 5.3 on page 32. When the FCPS-24S power supply is in an inactive state (control module not active), a trouble on the power supply will result in an open circuit condition on the control module output circuit (monitored by an End-of-Line Resistor across Terminals 5 &...
  • Page 34 Applications Remote Supply With Resettable and Nonresettable Power For addressable panel applications, an addressable monitor module can be used to monitor the trou- ble contact of the FCPS-24S and the resettable power connection from the FACP using an End-of- Line power supervision relay. If the FCPS-24S enters a trouble condition, the Normally Closed trouble contact will open and if the resettable power from the FACP is lost, the Normally Closed power supervision relay contact will open.
  • Page 35: Master Facp With Slave Fcps-24S Power Supply

    Master FACP with Slave FCPS-24S Power Supply Applications 5.5 Master FACP with Slave FCPS-24S Power Supply In this application, an FCPS-24S power supply, configured as a Slave unit, is connected to a master FACP programmed for synchronized output. The power supply should be set for synchronization which matches the FACP programming.
  • Page 36: Master Fcps-24S Power Supply Connected To Facp

    Applications Master FCPS-24S Power Supply Connected to FACP 5.6 Master FCPS-24S Power Supply Connected to FACP In this application, a master FCPS-24S power supply, set for synchronization, is connected to an FACP with nonsynchronized output. Internal Trouble Contact Standby Polarity Shown FACP FCPS-24S 1 2 3 4 5 6 7 8 9 10...
  • Page 37 Canadian Applications Applications NAC Outputs only Cut JP1 Battery - Battery - Host FACP FCPS Power Supply *If the SLC device does not match the one in this figure, refer to the SLC man- ual wiring conversion charts for legacy and newer versions of the modules. FCPS-24S Series Instruction Manual —...
  • Page 38: Section 6: Power Supply Requirements

    Section 6: Power Supply Requirements 6.1 Overview This section contains instructions and tables for calculating power supply currents in alarm and standby conditions. This is a four-step process, consisting of the following: Calculating the total amount of AC branch circuit current required to operate the system Calculating the power supply load current for non-fire and fire alarm conditions and calculating the secondary (battery) load Calculating the size of batteries required to support the system if an AC power loss occurs...
  • Page 39: Calculating The System Current Draw

    Calculating the System Current Draw Power Supply Requirements 6.3 Calculating the System Current Draw 6.3.1 Overview The power supply must be able to power all internal and external devices continuously during the non-fire alarm condition. To calculate the non-fire alarm load on the power supply when primary power is applied, use Calculation Column 1 in Table 6.3 on page 40.
  • Page 40 Power Supply Requirements Calculating the System Current Draw Table 6.3 contains three columns for calculating current draws. For each column, calculate the cur- rent and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calcu- lation Column 2 and Calculation Column 3 to Table 6.4 on page 41.
  • Page 41: Calculating The Battery Size

    Calculating the Battery Size Power Supply Requirements 6.4 Calculating the Battery Size Use Table 6.4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load determines the battery size (in AH) required to support the power supply under the loss of AC power.
  • Page 42 Notes FCPS-24S Series Instruction Manual — P/N 51977:J2 7/11/2014...
  • Page 43 Appendix A: Wire Requirements Connecting external system accessories to the main circuits must be carefully considered to ensure proper operation. It is important to use the correct type of wire, gauge and run length for each cir- cuit. The following table lists NAC wiring requirements for the FCPS-24S6 and FCPS-24S8 Field Charger Power Supply.
  • Page 44 Index Class A Converter Module 16 see also ZNAC-4 8 Class B Loss 8 see also Style Y 8 Loss Reporting Delay 27 Coded Input 10 AC fail Coded/Noncoded Input Selection 10 delay 23 coding see also AC loss reporting delay 23 NAC 8 AC loss compatibility...
  • Page 45 Index J–T current 11 voltage 11 output input circuit 8 circuit types 11 activation 8 maximum current 3.0 amps 11 compatibility 8 output circuit see also control 11 current 11 installation 14 maximum current 9 see also NAC output 11 Style 11 voltage rating 11 JP1 Jumper...
  • Page 46 W–Z Index troubles 26 power supply 8 wiring 9 AC power 10 power-limited 17 ZNAC-4 16 see also Class A Converter Module 8 FCPS-24S Series Instruction Manual — P/N 51977:J2 7/11/2014...
  • Page 47 Manufacturer Warranties and Limitation of Liability Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan.
  • Page 48 World Headquarters 12 Clintonville Road Northford, CT 06472-1610 USA 203-484-7161 fax 203-484-7118 www.notifier.com...

Table of Contents