Honeywell POL-200-TS User Manual page 9

Analogue loop verification tool
Hide thumbs Also See for POL-200-TS:
Table of Contents

Advertisement

POL-200-TS User Manual
To select between CLIP and ADVANCED Protocol please access the configuration screen and in
the button line select one of the two protocols available.
Lower Case or Capital Letter: in case that in the auto learn a Lower case letter appears please
confirm in the configuration that the correct protocol is selected between these difference op-
tions "Notifier", "Morley", "System Sensor" or "Honeywell HBS".
In case that in one address a device change the type ID or from lower case to capital letter, please
check the wiring in this device as its answer is not correct. Possible reason is a defective device
or noise due to interferences. Please also check that the device is not faulty or there is noise due
to interference.
A "?" Character in the ID type field can be indicative of a problem in the device or due to prob-
lems in the wiring line.
A "-" character in ID type may be indicative of duplicate address.
For each sampling POL-200-TS identifies the changes that have occurred since the previous sam-
pling, for that, the type of ID that identifies each address will appear in red or black. The red
color indicates that a change has occurred.
To get more details about each of the elements, select them by clicking directly on them or with
the help of the cursors and mark them by pressing the button
. Holding down this button
you will get the details of the selected item within the sampling table.
The PWs value is for Honeywell technical team references, PW1 should be around 150 +/- 10%
in Honeywell and Morley while around 300 +/- 10% for Notifier / System Sensor. Other values
outside these range should be reported to Honeywell technical support for advice.