IOM ADDRESS SET UP
Each IOM should have its own
address. The address could range
from 1 to 127. Never use zero as
IOM address as zero is reserved
for the master device.
Note: It is recommended not to
attach more than 4 IOM units to the
RS485 bus to maintain a
reasonable signal/response time
delay between the reader and
IOMs. Hence IOM addresses must
be from 1 to 4 only.
RS485 ID
RS485 ID
RS485 ID
RS485 ID
 
 
 
 
 
 
 
 
 
SUM all ON bit values 
SUM all ON bit values 
SUM all ON bit values 
SUM all ON bit values 
 
 
 
 
Never use address zero 
Never use address zero 
Never use address zero 
Never use address zero 
Fig.28. IOM Address set up
Honeywell IdentIPoint Intelligent Smartcard Readers
+
+
+
+
1
1
1
1
+
+
+
+
2
2
2
2
+
+
+
+
4
4
4
4
+
+
+
+
8
8
8
8
+
+
+
+
1 6
1 6
1 6
1 6
+
+
+
+
3 2
3 2
3 2
3 2
+
+
+
+
6 4
6 4
6 4
6 4
29
To work out the address, select a
combination of bit locations on the
DIP switch. Each bit has its own
value representation. The RS485
address is obtained by adding all
ON-bit values. E.g. Decimal value
37 will be obtained by turning ON
bits 1, 3 and 6 which equivalents to
1+4+32.
NOTE: Please refer to IdentIPoint
Hardware Installation Manual (doc.
no. 95-7767) for more details on
the following items:
Overall system architecture
Power supply installation
Detailed wiring descriptions
for readers, IOM and
peripheral devices
Power-over-Ethernet wiring
95-7771