2.16 TECHNICAL SPECIFICATIONS.
2.16.2.1 FUNDAMENTAL CURRENT
Accuracy:
2
2.16.3.1 AC CURRENT
Secondary Rated Current:
Frequency:
2.16.3.2 DIGITAL INPUTS
Voltage Level:
Recognition Time:
2.16.4.1 LOW RANGE
Rated DC Voltage:
Min./Max. DC Voltage:
2.16.4.2 HIGH RANGE
Rated DC Voltage:
Min./Max. DC Voltage:
Rated AC Voltage:
Min./Max. AV Voltage:
Power Consumption:
Proper backup time (date, time and log
memory) without power supply voltage
2-24
±1% at In
±3%Ifrom 0.5 to 2.0 In
1m 5 A depending on the selected model
50 / 60 Hz (The unit can be set to 50 or 60 Hz)
ground, secondary
300 Vdc maximum
< 4 ms
24 to 48 Vdc
19 / 58 Vdc
110 to 250 Vdc
88 / 300 Vdc
110 to 230 Vac @ 48 - 62 Hz
88 / 264 Vac @ 48 - 62 Hz
Max. = 10 W
> 1 week