5 SETTINGS
MENU
ADVANCED SETTINGS
PHASE TOC 51P
GEK-113188A
ADVANCED
MAIN SETTINGS
SETTINGS
PHASE TOC 51P
ENTER
Enable 51P
PHASE TOC 51P
Trip enable 51P
PHASE TOC 51P
Pickup 51P
PHASE TOC 51P
Curve 51P
PHASE TOC 51P
TD Mult 51P
PHASE TOC 51P
Def Time 51P
MIGII Digital Protection for Electrical Machines
5.3 ADVANCED SETTINGS
5.3.8 PHASE TOC 51P
ENTER
PHASE TOC 51P
Range: Yes/No
Default: No
Range: Yes/No
Default: Yes
Range: 0.1 – 30 FLC
Default: 0.5 FLC
Step: 0.1
Range: Extr. Inverse/ Definite Time/ User/
Mod Inverse/ Very Inverse
Default: Definite Time
Range: 0.05 – 2 (IEC) or 0.5 – 20 (ANSI)
Default: 0.5 (IEC) or 5 (ANSI)
Range: 0 – 600 s
Default: 0 s
Step: 0.1
5
5-17