9 RELAY COMMISSIONING
9.16 THERMAL IMAGE ELEMENT (49)
9.16.2 INVERSE SEQUENCE TEST
Apply 0.5 X In pure direct sequence current (0.5 x In to each phase). The relay should trip in 10.92 s (±5%).
9.16.3 SINGLE-PHASE SIGNAL TEST
Apply 1.2 x In only to phase A. The relay should trip in 11.37 s (±5%).
9
GEK-113188A
MIGII Digital Protection for Electrical Machines
9-19