Settings - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

Section 3
Basic functions
3.8.2.3
58
Table 25:
SMAI_20_1 Output signals
Name
Type
SPFCOUT
REAL
AI3P
GROUP SIGNAL
AI1
GROUP SIGNAL
AI2
GROUP SIGNAL
AI3
GROUP SIGNAL
AI4
GROUP SIGNAL
AIN
GROUP SIGNAL

Settings

Only values 1-3 of the parameter GlobalBaseSel should normally be
used. The values 1-3 refer to the global base value groups Phase Grp
1, Phase Grp 2 and Phase Grp 3 correspondingly (BASEPH1,
BASEPH2 and BASEPH3 in PCM600). The selection affects the
actual limit for frequency calculation set by MinValFreqMeas which
by default is 10% of the Voltage base Val PP in the selected group.
The values 4-6 refer to Residual Grp 1, Residual Grp 2 and Residual
Grp 3 (BASERES1, BASERES2 and BASERES3 in PCM600)
correspondingly and they are typically not to be used in this
connection.
Description
Number of samples per fundamental cycle from
internal DFT reference function
Grouped three phase signal containing data from
inputs 1-4
Quantity connected to the first analog input
Quantity connected to the second analog input
Quantity connected to the third analog input
Quantity connected to the fourth analog input
Calculated residual quantity if inputs 1-3 are
connected
PML630/Compact Load-Shedding Solution
1MRS757256 F
Technical Manual