Settings; Operation Principle - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

1MRS757256 F
3.7.3.3
3.7.4
PML630/Compact Load-Shedding Solution
Technical Manual
Table 23:
ACTVGRP Output signals
Name
Type
GRP1
BOOLEAN
GRP2
BOOLEAN
GRP3
BOOLEAN
GRP4
BOOLEAN
SETCHGD
BOOLEAN

Settings

The function does not have any parameters available in LHMI or PCM600.

Operation principle

Parameter setting groups (ACTVGRP) function has four functional inputs, each
corresponding to one of the setting groups stored in the IED. Activation of any of these
inputs changes the active setting group. Five functional output signals are available for
configuration purposes.
A setting group is selected by using the LHMI, from a front connected personal
computer, remotely from the station control or station monitoring system or by
activating the corresponding input to the ACTVGRP function block.
Each input of the function block can be configured with PCM600 to connect to any of
the binary inputs in the IED.
The external control signals are used for activating a suitable setting group when
adaptive functionality is necessary. Input signals that should activate setting groups
must be either permanent or a pulse exceeding 400 ms.
More than one input may be activated at the same time. In such cases the lower order
setting group has priority. This means that if, for example, both group four and group
two are set to activate, group two is the one activated.
Every time the active group is changed, the output signal SETCHGD is sending a
pulse.
The parameter MaxNoSetGrp defines the maximum number of setting groups in use
to switch between.
Basic functions
Description
Setting group 1 is active
Setting group 2 is active
Setting group 3 is active
Setting group 4 is active
Pulse when setting changed
Section 3
55

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pml630

Table of Contents