each positive edge of the input respectively. The maximum count-up speed is 10
pulses per second. The maximum counter value is 10000. The counter stops at 10000
and no restart takes places, even if the count exceeds 10000.
A mechanism for limiting the number of writings per time period is included in the
product to avoid the risk of the flash memory becoming worn out due to too many
writings. As a result, it can take a long time, up to one hour, before a new value is
stored in the flash memory. If a new CNTGGIO value is not stored before auxiliary
power interruption, it is lost. The CNTGGIO-stored values in the flash memory are,
however, not lost at an auxiliary power interruption.
The function block also has an input BLOCK. The activation of the BLOCK input
blocks all six counters. The inputs can be used for blocking the counters at testing, for
example.
All inputs are configured via PCM600.

Reporting

The content of the counters can be read in the LHMI.
Reset of counters can be performed in the LHMI and with a binary input.
Reading of the content and resetting of the counters can also be performed remotely
with PCM600 or, for example, MicroSCADA.

Technical data

Table 42:
CNTGGIO Technical data
Function
Counter value
Maximum count up speed

Test mode functionality TESTMODE

Function block

TESTMODE
INPUT
ACTIVE
OUTPUT
SETTING
NOEVENT
GUID-C35CCC2C-B1A5-4626-8082-E5170FF4D6FB V1 EN
Figure 39:
Function block
Range or value
0-10000
10 pulses/second
Section 3
Basic functions
Accuracy
-
-
73