Settable Timer Function Block Timersetqt - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

Section 3
Basic functions
3.32.2.5
164
Table 178:
XORQT Output signals
Name
Type
OUT
BOOLEAN
NOUT
BOOLEAN
Settings
The function does not have any parameters available in LHMI or PCM600.

Settable timer function block TIMERSETQT

Function block
TIMERSETQT
INPUT
IEC09000303-1-en.vsd
IEC09000303 V1 EN
Figure 101:
Function block
Functionality
The Settable timer function block (TIMERSETQT) has pick-up and drop-out delayed
outputs related to the input signal. The timer has a settable time delay (t).
When the output changes value the timestamp of the output signal is updated. The
supported "quality" state bits are propagated from the input each execution to the
output. A change of these bits does not lead to an updated timestamp on the output.
Input
On
Off
IEC08000289 V2 EN
Figure 102:
TIMERSETQT function
Description
Output signal
Inverted output signal
ON
OFF
tdelay
IEC08000289-2-en.vsd
1MRS757256 F
tdelay
t
PML630/Compact Load-Shedding Solution
Technical Manual