1MRS757256 F
Table 187:
SRMEMORYQT Group settings (basic)
Name
Values (Range)
Memory
3.32.2.8
PML630/Compact Load-Shedding Solution
Technical Manual
Signals
Table 185:
SRMEMORYQT Input signals
Name
SET
RESET
Table 186:
SRMEMORYQT Output signals
Name
OUT
NOUT
Settings
Unit
Off
-
On

Reset-set function block RSMEMORYQT

Function block
RSMEMORYQT
SET
RESET
IEC09000302-1-en.vsd
IEC09000302 V1 EN
Figure 105:
Function block
Functionality
The Reset-set function (RSMEMORYQT) is a flip-flop with memory that can reset or
set an output from two inputs respectively. Each RSMEMORYQT function block has
two outputs, where one is inverted. The memory setting controls if the flip-flop after
a power interruption returns to its previous state or if it is reset.
Table 188:
RSMEMORYQT functionality
SET
RESET
1
0
0
1
1
1
0
0
Type
Default
Description
BOOLEAN
0
Input signal to set
BOOLEAN
0
Input signal to reset
Type
Description
BOOLEAN
Output signal
BOOLEAN
Inverted output signal
Step
Default
-
On
OUT
NOUT
OUT
NOUT
1
0
0
1
0
1
0
1
Section 3
Basic functions
Description
Operating mode of the memory function