GE AF-600 FP Series Design And Installation Manual page 73

Fan & pump drive
Hide thumbs Also See for AF-600 FP Series:
Table of Contents

Advertisement

RS-485 Installation and Set...
9.2.2 Status Word According to Drive
Profile (STW) (O-10 Control Word
Profile = Drive profile)
Illustration 9.2 Status Word
Bit
Bit = 0
00
Control not ready
01
Drive not ready
02
Coasting
03
No error
04
No error
05
Reserved
06
No error
07
No warning
08
Speed ≠ reference
09
Local operation
10
Out of frequency limit
9
9
11
No operation
12
Drive OK
13
Voltage OK
14
Torque OK
15
Timer OK
Table 9.7 Status Word Bits
Explanation of the Status Bits
Bit 00, Control not ready/ready
Bit 00 = '0': The frequency converter trips. Bit 00 = '1': The
frequency converter controls are ready but the power
component does not necessarily receive any power supply
(in case of external 24V supply to controls).
Bit 01, Drive ready
Bit 01 = '1': The frequency converter is ready for operation
but the coasting command is active via the digital inputs
or via serial communication.
Bit 02, Coasting stop
Bit 02 = '0': The frequency converter releases the motor. Bit
02 = '1': The frequency converter starts the motor with a
start command.
Bit 03, No error/trip
Bit 03 = '0' : The frequency converter is not in fault mode.
Bit 03 = '1': The frequency converter trips. To re-establish
operation, enter [Reset].
70
TM
AF-600 FP
Design and Installation Guide
Bit = 1
Control ready
Drive ready
Enable
Trip
Error (no trip)
-
Triplock
Warning
Speed = reference
Bus control
Frequency limit OK
In operation
Stopped, auto start
Voltage exceeded
Torque exceeded
Timer exceeded
DET-768b
Bit 04, No error/error (no trip)
Bit 04 = '0': The frequency converter is not in fault mode.
Bit 04 = "1": The frequency converter shows an error but
does not trip.
Bit 05, Not used
Bit 05 is not used in the status word.
Bit 06, No error/triplock
Bit 06 = '0': The frequency converter is not in fault mode.
Bit 06 = "1": The frequency converter is tripped and locked.
Bit 07, No warning/warning
Bit 07 = '0': There are no warnings. Bit 07 = '1': A warning
has occurred.
Bit 08, Speed≠ reference/speed = reference
Bit 08 = '0': The motor is running but the present speed is
different from the preset speed reference. It might e.g. be
the case when the speed accels/decels during start/stop.
Bit 08 = '1': The motor speed matches the preset speed
reference.
Bit 09, Local operation/bus control
Bit 09 = '0': [STOP/RESET] is activate on the control unit or
Local control in F-02 Operation Method is selected. You
cannot control the frequency converter via serial communi-
cation. Bit 09 = '1' It is possible to control the frequency
converter via the network / serial communication.
Bit 10, Out of frequency limit
Bit 10 = '0': The output frequency has reached the value in
F-18 Motor Speed Low Limit [RPM] or F-17 Motor Speed High
Limit [RPM]. Bit 10 = "1": The output frequency is within
the defined limits.
Bit 11, No operation/in operation
Bit 11 = '0': The motor is not running. Bit 11 = '1': The
frequency converter has a start signal or the output
frequency is greater than 0 Hz.
Bit 12, Drive OK/stopped, autostart
Bit 12 = '0': There is no temporary over temperature on
the inverter. Bit 12 = '1': The inverter stops because of over
temperature but the unit does not trip and will resume
operation once the over temperature stops.
Bit 13, Voltage OK/limit exceeded
Bit 13 = '0': There are no voltage warnings. Bit 13 = '1': The
DC voltage in the frequency converter's intermediate
circuit is too low or too high.