About Programming
4.
AN-10 Terminal 53 Low Voltage. Set minimum
external voltage reference on Terminal 53 at 0 V.
(This sets the minimum input signal at 0 V.)
Illustration 5.4 Analog Reference AN-10 Terminal 53 Low Voltage
5.
AN-11 Terminal 53 High Voltage. Set maximum
external voltage reference on Terminal 53 at 10 V.
(This sets the maximum input signal at 10 V.)
Illustration 5.5 Analog Reference AN-11 Terminal 53 High Voltage
6.
AN-14 Terminal 53 Low Ref./Feedb. Value. Set
minimum speed reference on Terminal 53 at 20
Hz. (This tells the frequency converter that the
minimum voltage received on Terminal 53 (0 V)
equals 20 Hz output.)
Illustration 5.6 Analog Reference AN-14 Terminal 53 Low Ref./
Feedb. Value
TM
AF-600 FP
Design and Installation Guide
7.
Illustration 5.7 Analog Reference AN-15 Terminal 53 High Ref./
Feedb. Value
With an external device providing a 0-10 V control signal
connected to frequency converter terminal 53, the system
is now ready for operation. Note that the scroll bar on the
right in the last illustration of the display is at the bottom,
indicating the procedure is complete.
Illustration 5.8 shows the wiring connections used to
enable this set up.
Illustration 5.8 Wiring Example for External Device Providing
0-10 V Control Signal (Frequency Converter Left, External Device
Right)
DET-768b
AN-15 Terminal 53 High Ref./Feedb. Value. Set
maximum speed reference on Terminal 53 at 50
Hz. (This tells the frequency converter that the
maximum voltage received on Terminal 53 (10 V)
equals 50 Hz output.)
5
5
35