GE AF-600 FP Series Design And Installation Manual page 69

Fan & pump drive
Hide thumbs Also See for AF-600 FP Series:
Table of Contents

Advertisement

Status Messages
Start fwd/rev
Stop
Trip
Trip lock
Table 8.4 Operation Status
NOTE
In auto/remote mode, the frequency converter requires
8
8
external commands to execute functions.
66
AF-600 FP
Start forward and start reverse were selected
as functions for two different digital inputs.
The motor will start in forward or reverse
depending on which corresponding terminal
is activated.
The frequency converter has received a stop
command from the keypad, digital input or
serial communication.
An alarm occurred and the motor is stopped.
Once the cause of the alarm is cleared, the
frequency converter can be reset manually by
pressing [Reset] or remotely by control
terminals or serial communication.
An alarm occurred and the motor is stopped.
Once the cause of the alarm is cleared, power
must be cycled to the frequency converter.
The frequency converter can then be reset
manually by pressing [Reset] or remotely by
control terminals or serial communication.
TM
Design and Installation Guide
DET-768b