Summary of Contents for GE AF-600 FP Metasys

  • Page 1 GE Consumer & Industrial Electrical Distribution AF-600 FP Metasys Operating Instructions...
  • Page 2: Table Of Contents

    AF-600 FP Metasys Contents 1 Overview Software Version Introduction Copyright, Limitation of Liability and Revision Rights About this Manual References 2 Instructions Abbreviations and Definitions Network Connection Hardware Set-up Drive Parameters 3 Appendix Analog Inputs (AI) Binary Inputs (BI) Analog Outputs (AO)
  • Page 3 AF-600 FP Metasys...
  • Page 4: Overview

    AF-600 FP Metasys 1 Overview 1.1.1 Software Version AF-600 FP Software version: 2.12 This guide can be used with all AF-600 FP frequency converters with software version 2.12 or later The actual software version number can be read from par. ID-43 Software Version.
  • Page 5: Copyright, Limitation Of Liability And Revision Rights

    In no event shall GE be liable for direct, indirect, special, incidental, or consequential damages arising out of the use, or the inability to use information contained in this manual, even if advised of the possibility of such damages. In particular, GE is not responsible for any costs, including but not limited to those incurred as a result of lost profits or revenue, loss or damage of equipment, loss of computer programs, loss of data, the costs to substitute these, or any claims by third parties.
  • Page 6: Instructions

    AF-600 FP Metasys 2 Instructions 2.1.1 Abbreviations and Definitions Abbreviations and definitions Acknowledge Internal Floating Points Internal Integers Analog Inputs Analog Outputs Binary Inputs Binary Outputs Change Of State HPFB High Performance Field Network Johnson Controls Inc. developers of the METASYS N2 protocol...
  • Page 7: Hardware Set-Up

    AF-600 FP Metasys 2.1.3 Hardware Set-up RS485 Network Connection: One or more frequency converters can be connected to a control (or master) using the RS485 standardized interface. Terminal 68 is connected to the P signal (TX +, RX+), while terminal 69 is connected to the N signal (TX-,RX-). If more than one frequency converter is connected to a master, use parallel connections.
  • Page 8: Drive Parameters

    AF-600 FP Metasys 2.1.4 Error Codes Error codes Error Code 00 is issued after power up or after a time out where all overridden points were released, as long as no Identify yourself command has been issued by the master.
  • Page 9 AF-600 FP Metasys 2.1.6 General Commands (Acknowledged) NPA Object DRIVE Response Command Subcommand Attribute Message Type Error Code Comments The slave is to respond with any data points, Poll Message analog or binary I/O that have been flagged No Acknowledge...
  • Page 10 AF-600 FP Metasys 2.1.7 Analog Input Commands (Acknowledged) DRIVE Re- Subcom- Attribute Command Region NPA Object no. Attribute Message Type Comments sponse mand Read Object Configuration at- 0-23 Byte Read Analog Input tribute associated with each individual point Read Object Status attribute...
  • Page 11 AF-600 FP Metasys 2.1.8 Analog Input Commands (Not Acknowledged) DRIVE Com- Region NPA Object no. Attribu- Attribute Message Type Error Comments Response mand te No. Code 0-23 Float Read Analog Input Read Linear Ranging Parameter 1 attribute associated with each individual point.
  • Page 12 AF-600 FP Metasys 2.1.9 Analog Output Commands (Acknowledged) DRIVE Command Region NPA Object no. Attribute No. Attribute Message Type Comments Response command Byte Read Analog Output Read Object Configuration attrib- ute associated with each individual point Byte Read Analog Output Read Object Status attribute asso-...
  • Page 13 AF-600 FP Metasys 2.1.10 Analog Output Commands (Not Acknowledged) DRIVE Command Region NPA Object no. Attribute No. Attribute Message Type Error Comments Response Code Float Read Analog Output Read Low Linear Ranging Parameter attribute associated with each individual point. (JCI use only)
  • Page 14 AF-600 FP Metasys 2.1.11 Binary Input (BI) Commands (Acknowledged) DRIVE Command Subcom- Region NPA Object no. Attribute No. Attribute Message Type Comments Response mand 0-135 Byte Read Binary In- Read Object Configuration at- tribute associated with each individual point 0-135...
  • Page 15 AF-600 FP Metasys 2.1.13 Binary Output Commands (Acknowledged) DRIVE Com- Subcom- Region NPA Object Attribute No. Attribute Message Type Comments Response mand mand 0-10 Byte Read Binary Output Read structure attributes associ- ated with each individual point 0-10 Byte Read Binary Output Read structure attributes associ-...
  • Page 16 AF-600 FP Metasys 2.1.15 Internal Integers (ADI) Commands (Acknowledged) DRIVE Command Subcom- Region NPA Object no. Attribute No. Attribute Message Type Comments Response mand 0-254 Integer Read Internal Pa- Read Object Status associ- rameter of object ated with each individual...
  • Page 17 AF-600 FP Metasys 2.2.1 Start-up of the Frequency Converter Use the frequency converter keypad mounted either on the drive or remote. Use the Extended Menu key to access the O-## group parameters (Options / Comms). The settings shown below are typical. Some settings may be changed to meet the application requirements. The settings below will serve as a good starting reference.
  • Page 18 AF-600 FP Metasys Example 3: Over-ride analog output, speed (50%) change command: Setting: Device address Char1 command Char1 subcommand Char2 region Char2 object number (NPA) Char8 override value * 4E 00 00 00 override value = 50% speed (IEEE floating point, format)
  • Page 19 AF-600 FP Metasys 2.2.3 Status Update Request A Status Update Request will cause the drive to report its current operating status. The status codes, descriptions and associated alarms are shown in the chart below. The Device Status Code consists of two parts. The Least Significant Byte, (LSB) of the hex number is the Alarm Number. The Most Significant Byte (MSB) indicates if the alarm is a normal trip (01) that can be reset automatically or manually, or if the alarm is a trip lock (02) requiring cycling power to the drive.
  • Page 20 AF-600 FP Metasys 2.2.4 Override/Override Release Commands and Time Out, O-04 (Setting [20], N2 Override release) The way the overridden points are released is very important to the way the drive will behave during the override release time out or for release commands issued by the N2 master.
  • Page 21 AF-600 FP Metasys The drawing below illustrates the AI COS handling. For AI: Alarm Enable or Warning Enable must be set in the Object Configuration Attribute (Attribute 1). Low/High Alarm limits (Attribute 8, 11) or Low/High Warning limits (Attribute 9, 10) must be programmed. Differential Value (Attribute 12) must also be programmed.
  • Page 22: Appendix

    AF-600 FP Metasys 3 Appendix 3.1.1 Analog Inputs (AI) Unit Description Range AF-600 FP Par. Number Reference [%] DR-02 Reference [Unit] DR-01 Feedback DR-52 Frequency DR-13 User defined readout DR-09 Current DR-14 Power DR-10 Power DR-11 Output Voltage DR-12 DC Voltage...
  • Page 23: Binary Inputs (Bi)

    AF-600 FP Metasys 3.1.2 Binary Inputs (BI) Unit Description Range AF-600 FP Par. Number Timers Status 0=OK, 1=Limit Current Status 0=OK, 1=Limit Voltage Status 0=OK, 1=Limit Inverter Status 0=OK, 1 =Stall, Auto-start Running Status 0=Not Running, 1=Running Frequency Status 0=Out of Range, 1=In Range...
  • Page 24 AF-600 FP Metasys Binary Inputs (BI), continued.. Unit Description Range AF-600 FP Par. Number Reserved Reserved Drive Initialized 0=OK, 1=Alarm Option Change 0=OK, 1=Alarm Brake IGBT 0=OK, 1=Alarm Brake Resistor 0=OK, 1=Alarm 1.8V Supply Low 0=OK, 1=Alarm Mains Failure 0=OK, 1=Alarm...
  • Page 25 AF-600 FP Metasys Binary Inputs (BI), continued.. Unit Description Selection AF-600 FP Par. Number Braking 0=FALSE, 1=TRUE Braking Max 0=Remote ref., 1=Local ref. Brake Check Ok 0=FALSE, 1=TRUE Output Frequency Low 0=FALSE, 1=TRUE Output Frequency High 0=FALSE, 1=TRUE Output Current Low...
  • Page 26: Analog Outputs (Ao)

    AF-600 FP Metasys 3.1.3 Analog Outputs (AO) UNIT DESCRIPTION RANGED PAR. NUMBER -200 to 200 Proportionally mapped into the range Bus reference -32768 to 32767 Bus feedback 1 Please refer to [4] O-94 Bus feedback 2 Please refer to [4]...
  • Page 27: Internal Integers (Adi)

    AF-600 FP Metasys 3.1.4 Internal Integers (ADI) Unit Description Range Par. Number Language Selection K-01 Setup Copy Function K-51 Custom Readout Unit K-30 Large Readout K-23 Small Readout 1 K-20 Small Readout 2 K-21 Small Readout 3 K-22 Unit of Local Reference...
  • Page 28: Internal Floating Point (Adf)

    AF-600 FP Metasys 3.1.5 Internal Floating Point (ADF) UNIT DESCRIPTION RANGE PAR. NUMBER Max valuer of custom readout Please refer to K-30 Motor power P-07 Motor voltage F-05 Motor frequency F-04 Motor Current(IM.N) P-03 (mAmp) Motor nom. Speed P-06 Resonance damping...
  • Page 29 AF-600 FP Metasys Internal Floating Point (ADF), continued.. UNIT DESCRIPTION RANGE PAR. NUMBER Warning Current Low(I H-70 Warning Current High (I H-71 HIGH Warning Freq. Low(F H-72 Warning Freq. High(F H-73 HIGH Unit Warning Low Ref.(Ref H-74 Unit Warning High Ref.(Ref...
  • Page 30 AF-600 FP Metasys Internal Floating Point (ADF), continued.. UNIT DESCRIPTION RANGE PARAMETER NUMBER Control Timeout Function O-04 Control Timeout Time O-03 Option B Relay 1 ON Delay 0.01 to 600.00 E-26:6 Option B Relay 1 OFF Delay 0.01 to 600.00...
  • Page 31: Internal Integers (Adi)

    AF-600 FP Metasys 3.1.6 Internal Integers (ADI) UNIT DESCRIPTION RANGE PAR. NUMBER Language Selection K-01 Setup Copy Function K-51 Custom Readout Unit K-30 Large Readout K-23 Small Readout 1 K-20 Small Readout 2 K-21 Small Readout 3 K-22 Unit of Local Reference...
  • Page 32 AF-600 FP Metasys Internal Integers (ADI), continued.. UNIT DESCRIPTION RANGE PARAMETER NUMBER Trip Delay on Overload SP-25 PID Normal/Inverse CL-81 PID Anti Windup CL-91 Feedback 1 Conversion CL-01 Feedback 1 Source Unit CL-02 Feedback 2 Conversion CL-04 Feedback 2 Source Unit...
  • Page 33 Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE company. AF-600 FP is trademark of the General Electric Company.