Table 4. Fault Message and Recommended Troubleshooting (continued) .
Fault Code
Fault 34
CTL input was energized at
Control On
the wrong time for the
RM7838A. This fault implies
a field wiring error was
made.
Fault 35
Safety relay was off when it
Internal Fault
should be on or fuse has
blown.
Fault 36
Main valve terminal was off
Internal Fault
when it should be on.
Fault 37
Pilot (ignition) valve terminal
Internal Fault
was off when it should be
on.
Fault 38
Ignition terminal was off
Internal Fault
when it should be on.
Fault 39
V2S valve terminal was off
Internal Fault
when it should be on.
Fault 40
Safety relay was on when it
Internal Fault
should be off.
Fault 41
Main valve terminal was on
Main Valve On
when it should be off.
Fault 42
Pilot (ignition) valve terminal
Pilot Valve On
was on when it should be
(Pilot Valve 1 on- for
off.
EC78XX controls)
Fault 43
Ignition terminal was on
Ignition On
when it should be off.
Fault 44
V2S valve terminal, used as
Pilot Valve 2 On
a pilot, was on when it
should be off.
Fault 45
Low fire interlock switch
Low Fire Sw. Off
failure to close or stay
closed.
System Failure
1. Check wiring, correct any errors.
2. Reset and sequence the RM7838A.
3. If fault persists, replace the relay module.
1. Reset and sequence the 7800.
2. If fault persists, replace the relay module.
1. Reset and sequence the 7800.
2. If fault persists, replace the relay module.
1. Reset and sequence the 7800.
2. If fault persists, replace the relay module.
1. Reset and sequence the 7800.
2. If fault persists, replace the relay module.
1. Reset and sequence the 7800.
2. If fault persists, replace the relay module.
1. Reset and sequence the 7800.
2. If fault persists, replace the relay module.
1. Warning! Remove system power, turn off fuel supply.
2. Check wiring, correct any errors.
3. Inspect the Main Fuel Valve(s) and connections. Assure that
switches are functioning correctly and are not jumpered or welded.
4. Reset and sequence the 7800.
5. If the fault persists, replace the relay module.
1. Warning! Remove system power, turn off fuel supply.
2. Check wiring, correct any errors.
3. Inspect the Pilot Fuel Valve(s) and connections. Assure that switch
is functioning correctly and is not jumpered or welded.
4. Reset and sequence the 7800.
5. If the fault persists, replace the relay module.
1. Warning! Remove system power, turn off fuel supply.
2. Check wiring, correct any errors.
3. Inspect the Ignition terminal and connections. Assure that switch is
functioning correctly and is not jumpered or welded.
4. Reset and sequence the 7800.
5. If the fault persists, replace the relay module.
1. Warning! Remove system power, turn off fuel supply.
2. Check wiring, correct any errors.
3. Inspect the Pilot Fuel Valve 2 and connections. Assure that switch
is functioning correctly and is not jumpered or welded.
4. Reset and sequence the 7800.
5. If the fault persists, replace the relay module.
1. Check wiring, correct any errors.
2. Reset and sequence the 7800.
3. Use either the manual motor position to drive the motor to the Low
Fire position, or use the Run/Test Switch option, if available.
Sequence to the Low Fire position and place the switch in the Test
position. Adjust the Low Fire switch while in this state to insure that
it is closing properly.
4. While in the drive to Low Fire state, measure the voltage between
terminals 19 and G (ground). 120 Vac should be present. If not, the
switch adjustment is incorrect and/or the switch is defective and
should be replaced.
5. If steps 1-4 are correct and the fault still persists, replace the relay
module.
7800 SERIES S7800B DISPLAY MODULE
Recommended Troubleshooting
17
(continued)
65-0219—1