Table 4. Fault Message and Recommended Troubleshooting (continued) .
Fault Code
Fault 21
Running interlock fault
Running ILK
during Prepurge.
Fault 22
Lockout interlock fault
Lockout ILK
during Prepurge.
Fault 23
Combustion airflow
Airflow Switch
interlock fault during
Prepurge.
Fault 24
The flame interlock (relay
Internal Fault
module) was on when it
should have been off.
Fault 25
The flame interlock (relay
Internal Fault
module) was off when it
should be on.
Fault 26
The Manual Open Valve
Man-Open Sw. Off
Switch was off when it
should be on.
Fault 27
Start Switch was on during
Start Switch On
Prepurge.
System Failure
1. Check wiring; correct any errors.
2. Inspect the fan, assure that there is no blockage of the air intake
and that it is supplying air.
3. Assure that the Running Interlock switches are functioning properly
and that the contacts are free from contaminants.
4. Reset and sequence the 7800 to Prepurge (place the Run/Test
switch into the Test position, if available). Measure the voltage
between terminal 7 and G (ground). 120 Vac should be present.
5. If steps 1 through 4 are correct and the fault per-sists, replace the
relay module.
1. Check wiring; correct any errors.
2. Inspect the fan, assure that there is no blockage of the air intake
and that it is supplying air.
3. Assure that the Lockout Interlock switches are functioning properly
and that their contacts are free from contaminants.
4. Reset and sequence the 7800 to Prepurge (place the Run/Test
switch into the Test position, if available). Measure the voltage
between terminal 7 and G (ground). 120 Vac should be present.
5. If steps 1 through 4 are correct and the fault per-sists, replace the
relay module.
1. Check wiring; correct any errors.
2. Inspect the fan, assure that there is no blockage of the air intake
and that it is supplying air.
3. Assure that the Airflow Interlock switches are functioning properly
and that their contacts are free from contaminants.
4. Reset and sequence the 7800 to Prepurge (place the Run/Test
switch into the Test position, if available). Measure the voltage
between terminal 7 and G (ground). 120 Vac should be present.
5. If steps 1 through 4 are correct and the fault per-sists, replace the
relay module.
1. Reset and sequence the 7800.
2. If fault persists, replace the relay module.
1. Reset and sequence the 7800.
2. If fault persists, replace the relay module.
1. Check wiring, correct any errors.
2. Assure that the Manual Open Valve Switch is fully open.
3. Assure that the Manual Open Switch is functioning properly and that
the contact is free from contaminants.
4. Reset and sequence the RM7838B.
5. Assure that there is voltage going into the switch and coming out of
the switch when closed. Verify that the relay module is receiving
power at terminal 17.
6. If steps 1 through 5 are correct and the fault per-sists, replace the
relay module.
1. Start Switch held "on" too long.
2. Check wiring, verify that the Start Switch has been connected
correctly. Correct any errors.
3. Assure that the Start Switch is functioning properly and that the
contact is free from contaminants.
4. Reset and sequence the RM7838B to Prepurge, place the Run/Test
switch into the Test position. Assure that there is no power at
terminal 6 during Prepurge.
5. If steps 1 through 3 are correct and the fault per-sists, replace the
relay module.
7800 SERIES S7800B DISPLAY MODULE
Recommended Troubleshooting
15
(continued)
65-0219—1