Download Print this page

Honeywell MPA1C1 Installation Manual page 48

Access control unit

Advertisement

LED status for general troubleshooting
LED Status
LED PWR -
Green
LED ETH -
Green
LED T-IN -
Red
LED RUN -
Green
LED BLE -
Blue
Description
Power LED, automatically powers on when system is
powered from either DC or PoE.
Ethernet Link LED, automatically powers on when
MPA1C1 Ethernet has link to external Network switch.
Tamper LED, On when internal Accelerometer tamper
is activated.
Flashing twice when:
• Request to Exit (REX) inputs in triggered, or
released.
• Door contact (DrCnt) input is triggered, or
released.
• Tamper (T-LID) input is triggered, or released.
RUN Activity LED slowly blinks (1 second on, one
second off) in normal operation.
Blinks rapidly when the RESET button is pressed for
20 seconds.Turns OFF after 20 seconds of
continuous pressing of the RESET button.
Bluetooth LED for commissioning with Device Utility
App:
Blinks slowly: Bluetooth active, trying to connect.
ON: Bluetooth active and connected to mobile device
with Device Utility App.
OFF: Bluetooth is disabled after restart or after 30
minutes after reset. Bluetooth is OFF in normal
operations
47