Problem
The readers are
not responding to
card reads
Solution
Option 1: Be sure that OSDP readers
have been connected or are in OSDP
mode
Option 2: Set up the correct addressing
on the OSDP readers. Addresses other
than '00', '01' or '02' are not recognized.
Set the reader in one of these
addresses:
'00' for auto addressing
'01' for entry reader
'02' for exit reader
Option 3: Make sure that the reader
baud rate is set to 9600 Baud
Option 4: Make sure that the reader
accepts secure channel communication