Honeywell HVAC400x Applications Manual page 57

Variable frequency drives for variable torque applications
Table of Contents

Advertisement

Index
Parameter
Underload Fault (broken
P3.9.15
belt/dry pump)
Underload Protection:
P3.9.16
Field Weakening Area
Load
Underload Protection:
P3.9.17
Zero Frequency Load
Underload Protection:
P3.9.18
Time Limit
Response to Fieldbus
P3.9.19
Communication Fault
Slot Communication
P3.9.20
Fault
P3.9.21
Thermistor Fault
P3.9.22
SoftFill Timeout
Response to PID1
P3.9.23
Supervision Fault
Response to PID2
P3.9.24
Supervision Fault
P3.9.25
TempFault Signal
P3.9.26
TempAlarm Limit
P3.9.27
TempFault Limit
P3.9.28
TempFault Response
continued: Protections settings
Min
Max
Unit
0
3
10.0
150.0
%
5.0
150.0
%
2.00
600.00
s
0
4
0
3
0
3
0
3
0
3
0
3
0
6
-30.0 °C
200 °C
°C
-22 °F
392 °F
°F
-30.0 °C
200 °C
°C
-22 °F
392 °F
°F
0
3
57
HVAC400X – APPLICATION MANUAL
Default
ID
Description
0
713
See P3.9.2.
50.0
714
10.0
715
20.00
716
3
733
See P3.9.1.
2
734
See P3.9.2.
0
732
See P3.9.2.
2
748
See P3.9.2.
2
749
See P3.9.2.
2
757
See P3.9.2.
0 = Not Used.
1 = Temp. Input 1.
2 = Temp. Input 2.
0
739
3 = Temp. Input 3.
4 = Temp. Inputs 1-2.
5 = Temp. Inputs 2-3.
6 = Temp. Inputs 1-3.
130.0 °C
741
266 °F
155.0 °C
742
311 °F
0 = No response.
1 = Alarm.
2
740
2 = Fault (Stop according to stop
mode).
3 = Fault (Stop by coasting).
EN2B-0417GE51 R0719