Wizards; Pid Mini-Wizard - Honeywell HVAC400x Applications Manual

Variable frequency drives for variable torque applications
Table of Contents

Advertisement

2

WIZARDS

2.1

PID Mini-Wizard

The application wizard helps you to set the basic parameters that are related to the application.
To start the PID mini-wizard, set the value Activate to parameter P1.18 PID Mini-Wizard in the Quick Setup menu.
The default settings tell you to use the PID controller in the one feedback / one setpoint mode. The default control
place is I/O A, and the default process unit is %.
1
Make selections for Process unit (P3.13.1.4)
If your selection is other than %, you see the next questions. If you select %, the wizard goes directly to question 5.
2
Set a value for Process Unit Min (P3.13.1.5).
3
Set a value for Process Unit Max (P3.13.1.6).
4
Set a value for Process Unit Decimals (P3.13.1.7).
5
Set a value for Feedback 1 Source Selection (P3.13.3.3).
If you select an analog input signal, you see the question 6. With other selections, the wizard goes to question 7.
6
Set the signal range of the analog input.
7
Set a value for Error Inversion (P3.13.1.8).
8
Set a value for Setpoint Source Selection (P3.13.2.4).
If you select an analog input signal, you will see question 9. If you set Keypad Setpoint 1 or Keypad Setpoint 2 for
the value, the wizard will go directly to question 10. With other selections, the wizard will go to question 11.
9
Set the signal range of the analog input.
Set a value for Keypad Setpoint 1 (P3.13.2.1) and Keypad
10
Setpoint 2 (P3.13.2.2)
11
Using the sleep function.
If you enter the value Yes for question 11, you see the next three questions. If you enter the value No, the wizard is
completed.
12
Set a value for Sleep Frequency Limit (P3.13.2.7).
13
Set a value for Sleep Delay (P3.13.2.8)
14
Set a value for Wake-up Level (P3.13.2.9).
The PID mini-wizard is completed.
HVAC400X – APPLICATION MANUAL
More than one selection.
The range depends on the selection in question 1.
The range depends on the selection in question 1.
Range: 0-4.
See Table 39. Feedback settings.
0 = 0-10V / 0...20mA.
1 = 2-10V / 4...20mA.
See Table 19. Analog input settings.
0 = Normal.
1 = Inverted.
See
Table 38. Setpoint
0 = 0-10V / 0-20mA.
1 = 2-10V / 4-20mA.
See Table 19. Analog input settings.
Shows only if you select Keypad Setpoint 1 or
Keypad Setpoint 2 in question 8.
0 = No.
1 = Yes.
Range: 0.00-320.00 Hz.
Range: 0-3000 s.
The range depends on the set process unit.
15
settings.
EN2B-0417GE51 R0719