Description Of The Applications; Hvac400 Applications - Honeywell HVAC400x Applications Manual

Variable frequency drives for variable torque applications
Table of Contents

Advertisement

HVAC400X – APPLICATION MANUAL
P3.4.2
Pump
5.0
Fan
See table.
P3.4.2
Acceleration Time
P3.4.3
Deceleration Time
P3.2.4
Start Function
P3.2.5
Stop Function
P3.4.8
RampTimeOptimizerEnable
P3.4.10
RampTimeOptimizerMaxLimit
P3.3.1
MinFrequency
P3.1.2.7
U/F Ratio
Ramp time
400 V / 480 V
20 s
400-1P1 - 400-7P5 / C 0015 – C 0100
30 s
400-11P - 400-22P / C 0150 – C 0300
45 s
400-30P - 400-55P / C 0400 – C 0750
60 s
400-75P - 400-90P / C 1000 – C 1250
90 s
400-110 - 400-160 / C 1500 – C 2500
Set a value for Motor Nominal Speed (so that it agrees with
8
the nameplate).
Set a value for Motor Nominal Current (so that it agrees with
9
the nameplate).
After these selections, the Start-up wizard is completed. To start the Start-up wizard again, you have two alter-
natives: Go to either parameter P6.5.1 Restore factory defaults or parameter P1.21 Start-up Wizard. Then set the
value to Activate.
NOTE:
If there is an external RUN command on the I/O, the parameters Restore factory defaults (par. P6.5.1) or
the Startup Wizard will not work.
1.4

Description of the Applications

1.4.1

HVAC400 Applications

The HVAC drive contains a preloaded application for immediate use.
It is possible to control the drive from the keypad, the Fieldbus, your PC, or from the I/O terminal.
EN2B-0417GE51 R0719
P3.4.3
P3.2.4
5.0
1
See table.
1
Affected parameters
Ramp table for fan set-up
P3.2.5
P3.4.8
1
False
0
True
230 V
230-P55 - 230-4P0 / A 0007 – A 0050
230-5P5 - 230-11P / A 0075 – A 0150
230-15P - 230-30P / A 0200 – A 0400
230-37P - 230-45P / A 0500 – A 0750
230-55P / A 1000 – A 1250
Range: 24-19200.
Range varies.
10
P3.4.10
P3.3.1
60.0
20.0
120.0
20.0
P3.1.2.7
Untouched.
1