Honeywell HVAC400x Applications Manual page 138

Variable frequency drives for variable torque applications
Table of Contents

Advertisement

HVAC400X – APPLICATION MANUAL
P3.12.1.5: Assign to channel: TimeChannel1.
Interval 2
P3.12.2.1: ON Time: 09:00:00.
P3.12.2.2: OFF Time: 13:00:00.
P3.12.2.3: From Day: Saturday.
P3.12.2.4: To Day: Sunday.
P3.12.2.5: Assign to channel: TimeChannel1.
Timer 1
You can start the motor with digital input 4 on slot A during times other than those specified with the intervals. In
this case, the timer specifies the duration that the motor runs.
P3.12.6.1: Duration: 1800 s (30 min).
P3.12.6.2: Assign to channel: TimeChannel1.
P3.5.1.19: Timer 1: DigIn SlotA.4 (The parameter located in the digital inputs menu).
A
Interval 1
B
From = Monday
D
ON = 07:00:00 hrs
F
Interval 2
G
From = Saturday
I
ON = 09:00:00 hrs
Digital input 1
on Slot A
K
Fig. 36. TimeChannel1 is used as the control signal for the Start command instead of a digital input
A.
Interval 1.
B.
From = Monday.
C.
To Thursday.
D.
ON = 07:00:00 hrs.
E.
OFF = 17:00:00 hrs.
F.
Interval 2.
G.
From Saturday.
H.
To Sunday.
P3.12.1.1 ON TIME (ID 1464)
You can use this parameter to set the time of day when the output of the interval function is activated.
EN2B-0417GE51 R0719
To = Friday
OFF = 17:00:00 hrs
To = Sunday
OFF = 13:00:00 hrs
Timer 1
Duration = 1800 s
Legend
C
E
P Ctrl Signal 1A
Time channel 1
H
J
L
I.
ON = 09:00:00 hrs.
J.
OFF = 13:00:00 hrs.
K.
Digital input 1 on Slot A.
L.
Timer 1, Duration = 1800 s
M.
Signal Ctrl 1A.
N.
TimeChannel1.
O.
Start/Stop.
138
M
N
Start/Stop
O