P3.5.1.42 FIELDBUS CONTROL (ID 411)
You can use this parameter to select the digital input signal that switches the control place and the frequency
reference source to Fieldbus (from I/O A, I/O B, or Local control).
P3.5.1.43 KEYPAD CONTROL (ID 410)
You can use this parameter to select the digital input signal that switches the control place and the frequency
reference source to Keypad (from any control place).
P3.5.1.44 RESET KWH TRIP COUNTER (ID 1053)
You can use this parameter to select the digital input signal that resets the kWh Trip Counter.
P3.5.1.45 PARAMETER SET 1/2 SELECTION (ID 496)
You can use this parameter to set the digital input that selects the parameter set to be used.
The parameter gives the digital input which is used to select Parameter Set 1 or Set 2. The function is enabled if
other slots than DigIN Slot0 are selected to this parameter. The selection of the parameter set can be made and
the set changes only when the drive is stopped.
Contact Open = Parameter Set 1 is set as the active set
Contact Closed = Parameter Set 2 is set as the active set
NOTE:
Parameter values are stored to Set 1 and Set 2 with parameters B6.5.6 Save to Set 1.
P3.5.1.46 FAULT RESET OPEN (ID 213)
You can use this parameter to select the digital input signal that resets all active faults. Active faults are reset when
the state of the digital input changes from closed to open (falling edge).
P3.5.1.47 DISABLE TIMER FUNCTION (ID 1499)
You can use this parameter to select the digital input signal that enables/disables all timer functions.
10.5.3

Analog Inputs

P3.5.2.1 AI1 SIGNAL SELECTION (ID 377)
You can use this parameter to connect the AI signal to the analog input of your choice. Connect the AI signal to the
analog input of your choice with this parameter.
P3.5.2.2 AI1 FILTER TIME (ID 378)
You can use this parameter to filter out disturbances in the analog input signal. This parameter gives the filtering
time for the analog signal. The filtering function is disabled when the filtering time is 0.
P3.5.2.3 AI1 SIGNAL RANGE (ID 379)
You can use this parameter to change the range of the analog signal. The value of this parameter is bypassed if
the custom scaling parameters are used in P3.5.2.4 and P3.5.2.5.
P3.5.2.4 AI1 CUSTOM MIN (ID 380)
You can use this parameter to adjust the range of the analog input signal between -160% and 160%.
P3.5.2.5 AI1 CUSTOM MAX (ID 381)
You can use this parameter to adjust the range of the analog input signal between -160% and 160%.
HVAC400X – APPLICATION MANUAL