Configuring And Wiring Detectors - Honeywell SS4-AI Installation Manual And Operating Manual

Infrared (ir) digital electro-optical fire detector
Table of Contents

Advertisement

2.4
HONEYWELL
Figure 4: Model SS4-AI Detector Enclosure Rear View

Configuring and Wiring Detectors

To configure and wire a Model SS4-AI Detector, its module has to be
removed from the enclosure. After the configuration settings and wiring
connections are made, re-install the module in the enclosure.
Exercise caution while performing this procedure. Do not touch the
detector elements on the front of the Model SS4-AI Detector modules. If
they are accidentally touched, clean them as instructed in Section 3.2,
Cleaning Windowed Enclosures and Detectors.
Observe static protection safeguards while handling Model SS4-AI Detector
modules. Properly wear a wrist strap connected to earth ground.
1. REMOVE THE DETECTOR MODULE FROM ITS ENCLOSURE.
a. With electrical power off, loosen the Allen-head screw at the
base of the metal enclosure top windowed cover. (Double
check that electrical power is off by seeing that the Detector's
LED's do NOT blink for at least 10 seconds.)
b. Unscrew the top windowed cover and set it aside with its "O"
ring. Keep both clean.
c. Loosen/remove the three slot headed screws located on the top
circuit board. (Some models use captive screws that should not
be removed from the circuit board).
d. Gently lift out the module, sliding it along the three metal
standoffs.
OPERATOR MANUAL // SECTION 2: INSTALLATION
11

Advertisement

Table of Contents
loading