Honeywell SS4-AS Installation Manual And Operating Manual

Honeywell SS4-AS Installation Manual And Operating Manual

Multi-spectrum digital electro-optical fire detector

Advertisement

Installation Guide and Operating Manual
Multi-Spectrum Digital
Electro-Optical Fire Detector
Model SS4-AS/-AS2
For Special Applications
(Optimized for Hydrogen, Silane, Methanol, Ethanol, and Methane)
Stand-Alone Relay Mode or 4-20 mA Output Option

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell SS4-AS

  • Page 1 Installation Guide and Operating Manual Multi-Spectrum Digital Electro-Optical Fire Detector Model SS4-AS/-AS2 For Special Applications (Optimized for Hydrogen, Silane, Methanol, Ethanol, and Methane) Stand-Alone Relay Mode or 4-20 mA Output Option...
  • Page 2 In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.
  • Page 3 It may also be used to alert against unsafe practices. CAUTION: Symbol on the equipment refers the user to the product manual for additional information. The symbol appears next to required information in the manual. HONEYWELL...
  • Page 4: Table Of Contents

    2.2.3 Configuring the Detector Module............16 2.2.4 Wiring the Detector Module..............17 2.2.5 Wiring the SS4-AS/-AS2 Detector for 4 or 20 mA Current Mode Operation (Optional) ..............18 2.2.6 Wiring the Detector Relays ..............19 2.2.7 Replacing the Detector Module in the Enclosure........19 Enclosure Installation (optional) ................
  • Page 5 4-20 mA Option (MA420-4) ................. 27 Detector Mounts (SM2 or SM4) ................27 Test Lamp (FT2045 or FT-2145)................. 27 SECTION 6 DETECTOR LABEL DRAWINGS ............. 28 INDEX ......................29 Read and understand this manual before installing or operating equipment. HONEYWELL...
  • Page 6: Approvals

    OPERATOR MANUAL // APPROVALS APPROVALS The Model SS4-AS/-AS2 Multi-Spectrum Fire Detectors have been manufactured in compliance with the requirements of the ISO-9002 standard and have been approved by: • California State Fire Marshal (CSFM) • Factory Mutual (FM) • Canadian Standards (CSA) •...
  • Page 7: Technical Description

    Features and Specifications 1.1.1 General Description The Model SS4-AS/-AS2 Multi-Spectrum Electro-Optical Fire/Flame Detectors are fast-reacting (within 5 seconds), digital, configurable, microprocessor-based, “smart” units. This Detector has sensitivity to Type A, B, and C flaming fires. They are optimized for detection of hydrogen, ethanol, methanol, and methane (natural gas) fires.
  • Page 8 Dual LEDs blink every 10 seconds Fault Declared: One LED turns ON solid until the fault is cured Re-calibrate when: Both LEDs flash ON and OFF rapidly Fire Declared: Both LEDs ON solid (one LED blinks during first few seconds) HONEYWELL...
  • Page 9: Applications

    Fault relay: N.O. and N.C. contacts 1.1.2 Applications Applications of the Model SS4-AS/-AS2 Detectors include storage warehouses of Ethanol, Methanol, and Methane (Natural Gas) and Hydrogen gas, among others. 1.1.3 Detector Locations For unobstructed performance, considering Detector locations in application...
  • Page 10: Stand-Alone Operation

    FS2000 System. FS2000 System Operation For FS2000 System operation, the Model SS4-AS/-AS2 Fire and Fault signals are sent digitally to the FS2000 System Controller using the four wire FS2000 FireBus. The FireBus provides 24 Volt DC power for the Detector and RS-485 digital communication (Refer to Honeywell Analytics document MN0003: "FS2000 FIRE EARLY WARNING SYSTEM - INSTALLATION and...
  • Page 11: Overview

    Overview 1.4.1 Model SS4-AS/-AS2 Detector Version SS4-AS: There are two (2) LEDs on the Model SS4-AS Detector that indicate the state of the Detector. During normal operation both LEDs will blink every 10 seconds. If the Detector alarms to a fire, it energizes the Fire relay and turns on both LEDs in the following sequence.
  • Page 12: Detection Range And Field-Of View

    TECHNICAL DESCRIPTION 1.4.2 Detection Range and Field-of View The SS4-AS detection range is field adjustable between 15 and 60 ft. in 15 ft. increments to an industry-standard one square foot heptane, gasoline, kerosene, or isopropyl alcohol pan fire within 5 seconds.
  • Page 13: Configuration Settings

    Sensitivity to 1 Sq. Ft. Gasoline Pan Fire Configuration Settings The SS4-AS/-AS2 Detector may be reconfigured in the field and thus optimized for special applications. The configuration of the Detector is set from a DIP switches located on the middle circuit board of the Detector Module. The DIP switch settings for each configuration are listed in Table 2.
  • Page 14 Latching or Non-Latching mode. The Factory setting for the SS4-AS is Latching and the SS4-AS2 is Non-Latching. If the SS4-AS or SS4-AS2 Latching mode is selected, the Fire or Verify Relay will energize and Red LEDs will remain illuminated until the Detector power is cycled (power is turned off then on).
  • Page 15: Testing

    1.6.3 Manual Testing For manual testing, the SS4-AS/-AS2 Detector may be exposed to an actual industry standard open flame or to a Test Lamp simulating a fire. It is mandatory to use the Honeywell Analytics handheld UV/IR Test Lamp Model No. FT-2045 or FT-2145 with SS4 Fire Detectors.
  • Page 16: Installation

    SECTION 2 INSTALLATION Installation Instructions This section describes the installation of the Model SS4-AS/-AS2 Detector for the Stand-Alone relay mode. It is recommended that junction boxes be used to wire the Detectors. Determine the configuration settings for the device(s) and the...
  • Page 17: Power Supply Considerations

    2.1.4 Power Supply Considerations The Model SS4-AS/-AS2 Detector uses 24 Volts DC at a maximum current of 75 mA (with the 4-20 mA option the maximum supply current is 95 mA). Make sure the Panel's power supply can withstand the load current of the total number of Detectors connected to it.
  • Page 18: Wiring The Detector Module

    RS-485( + ) +24 VDC Power ( + ) Verify Relay *Fault Relay * Fault relay is shown in the energized condition during normal operation (No Fault). Figure 2: Model SS4-AS/-AS2 Detector Wiring (Bottom View of SS4-AS/-AS2 Detector Module) HONEYWELL...
  • Page 19: Wiring The Ss4-As/-As2 Detector For 4 Or 20 Ma Current Mode Operation (Optional)

    OPERATOR MANUAL // SECTION 2 INSTALLATION 2.2.5 Wiring the SS4-AS/-AS2 Detector for 4 or 20 mA Current Mode Operation (Optional) For applications requiring a 4-20 mA analog output, order the Detector with the Optional 4-20 mA Module Assembly, P/N MA420-4. The module must be Factory installed and certified along with the Detector.
  • Page 20: Wiring The Detector Relays

    Mount the swivel-mount to the wall assuring correct orientation. c. Install the mounting bracket onto the Model SS4-AS/-AS2 Detector enclosure using the #¼-20 or #6 mm screws and nuts provided. If oriented correctly, the outside contours of the mounting ears on the Detector enclosure and the ends of the bracket will match.
  • Page 21 OPERATOR MANUAL // SECTION 2 INSTALLATION 2.95 2.00 4.26 4.86 0.295 Dia. 4.7” approx. Figure 4: Model SM2 Swivel Mount Figure 5: Model SM4 Stainless Steel Swivel Mount HONEYWELL...
  • Page 22 OPERATOR MANUAL // SECTION 2 INSTALLATION 1.50 4.38 2.40 0.67 2.09 1.10 4.66 Figure 6: Model SS4-AS/-AS2 Detector Enclosure - Side View Figure 7: Model SS4-AS/-AS2 Detector Enclosure - Rear View HONEYWELL...
  • Page 23: Troubleshooting And Maintenance

    TROUBLESHOOTING AND MAINTENANCE Model SS4-AS/-AS2 Detector Faults The Model SS4-AS/-AS2 Detector issues a Fault (or Trouble) condition by de- energizing the Fault Relay (J5 connector). The following are Detector Faults: a. Temperature Fault: The Detector faults if the internal temperature during operation rises above 85°C or falls below -40°C causing both...
  • Page 24: Cleaning Windowed Enclosures And Detectors

    TROUBLESHOOTING AND MAINTENANCE Cleaning Windowed Enclosures and Detectors The optical window (lens) of the Model SS4-AS/-AS2 Detector should be cleaned periodically on a regular maintenance schedule. For clean area applications, perhaps monthly cleaning schedule will be sufficient. For extremely contaminated application environments, such as truck filling stations with presence of black carboneous smoke, daily cleaning schedule may be necessary.
  • Page 25: Detector Repair

    Return the defective module to the factory for repair service. There are no user serviceable parts in the detector module If the Model SS4-AS/-AS2 Module must be shipped back to the factory for repair, it MUST be packed in static protective material. If not available, the Module should be carefully wrapped with aluminum foil.
  • Page 26: Detector Connections & Switch Options

    Fire Relay Common Fire Relay Normally Open FAULT RELAY (Energized) FIRE VERIFY RELAY Fault Relay Normally Open Verify Relay Common Fault Relay Common Verify Relay Normally Open Fault Relay Normally Closed Verify Relay Common Fault Relay Common Verify Relay Normally Closed HONEYWELL...
  • Page 27: Verification Time

    Set to detect an industry standard 1 sq. ft. fire at 30 ft. on axis. open closed Set to detect an industry standard 1 sq. ft. fire at 45 ft. on axis. Factory setting closed closed Set to detect an industry standard 1 sq. ft. fire at 60 ft. on axis. HONEYWELL...
  • Page 28: Optional Accessories

    The 4-20 mA module is by Factory Mutual (FM) recognized device to be used with all approved SS4 type Detectors. Honeywell Analytics is required by FM to install this device at the factory and certifies this option along with the Detector.
  • Page 29: Detector Label Drawings

    -40C to Polished Black Stainless Steel +85C +75C +60C LB-6093- -40C to -40C to -40C to 0.020' Al 1100-Hl4 Black White +85C +75C +60C LB-6093- 0.020' 316 -40C to -40C to -40C to Polished Black Stainless Steel +85C +75C +60C HONEYWELL...
  • Page 30: Index

    ESD ..........15 Stand-Alone ........9 FireBus ......... 9 Static Damage......15 FireBus Swivel Mount........ 19 Wiring ........15 Test Lamp ........27 Grounding ........15 Test Source..... 11, 12, 14 Theory of Operation ....10 Troubleshooting ......22 HONEYWELL...
  • Page 31 Honeywell Analytics warrants its Products against defects in material and workmanship under normal use and service for a period of two (2) years from the date of shipment as described herein. Honeywell Analytics, at its option, will repair or replace, at no charge, such products found to be defective during the warranty period provided that they are returned in accordance with the terms of this warranty.
  • Page 32 Honeywell Analytics Asia Pacific Co., Ltd. #701 Kolon Science Valley (1) 43 Digital-Ro 34-Gil, Guro-Gu Seoul, 152-729 Korea Email: analytics.ap@honeywell.com Internet These Honeywell websites may be of interest to Industry Solution customers. Honeywell Organization Corporate www.honeywell.com Honeywell Analytics www.honeywellanalytics.com Telephone Contact us by telephone at these numbers.
  • Page 33 1998M0912 Rev. A July, 2014 © 2014 Honeywell International Inc.

This manual is also suitable for:

Ss4-as2Ss4-aSs4-a2

Table of Contents