Honeywell SS4-AI Installation Manual And Operating Manual page 13

Infrared (ir) digital electro-optical fire detector
Table of Contents

Advertisement

HONEYWELL
2. CONFIGURING THE DETECTOR MODULE.
a. Set the Dip switches located on the center PC board of the
detector module to the desired settings. The factory settings
should be appropriate for most applications. See Dip Switch
Setting Chart for switch functions and settings.
3. WIRE THE DETECTOR MODULE.
a. Insert the cables into the metal enclosure base through one of
the conduit openings.
Figure 5: Model SS4-AI Detector Wiring
Bottom View of SS4-AI Detector Module
b. Then connect the 24 volt DC Power Supply wires into the J1 or
J2 connector and firmly tighten down the two slotted screws
with a small screwdriver. DO NOT CONNECT ANY WIRES TO
Pin 2 or Pin 3. Do NOT over tighten or the screws may strip or
break. Refer to Figure 4, Model SS4-AI Detector Wiring.
Pin 1
Black
Ground (-)
OPERATOR MANUAL // SECTION 2: INSTALLATION
Pin 2
Pin 3
Green or Blue
White or Yellow
NOT USED
NOT USED
Pin 4
Red
Power (+)
12

Advertisement

Table of Contents