RM7898A 7800 SERIES VALVE PROVING PRIMARY RELAY MODULES
MV1—Wired to terminal 9. It is located at the most
upstream position of the main gas valve train.
VPS—Valve Proving Switch (Rated 1/2 of main valve inlet
pressure).
MV2—Wired to terminal 21. It is the main valve located
closest to the burner.
The Pre-Ignition Interlock switch or Proof of Closure for
Terminal 20 can be installed on MV1, MV2, or as a series
connection through both valves.
WARNING
Explosion Hazard
Can cause severe injury, death or property
damage.
Be sure to select adequate testing times when the
Valve Proving feature is enabled. A shorter time can
result in inadequate leak testing of the valves.
This document provides installation and static checkout
instructions. Other applicable publications are:
Publication
No.
S7800A2142 4-line LCD Keyboard Display
32-00110
Module Product Data
Tester for the 7800 SERIES System with
32-00160
valve proving systems
204729A/C KDM NEMA4 Covers for 4-line
32-00166
LCD KDM
65-0084
Q7800A,B 22-Terminal Wiring Subbase
Product Data
65-0288
S7800A1142 2-line VFD Keyboard
Display Module Product Data
65-0091
S7810A Data ControlBus™ Module Product
Data
65-0095
S7820 Remote Reset Module Product Data
65-0097
221729C Dust Cover Installation
Instructions
65-0101
S7830 Expanded Annunciator Product
Data
65-0109
R7824, R7847, R7848, R7849, R7851,
R7861, R7886 Flame Amplifiers for the
7800 SERIES Product Data
65-0131
221818A Extension Cable Assembly
Product Data
65-0229
7800 SERIES Relay Modules Checkout
and Troubleshooting Product Data.
65-0249
S7810M ModBus Module
32-00209-03
Product
2

SPECIFICATIONS

Electrical Ratings (See Table 4):
Voltage and Frequency:
RM7898: 120 Vac (+10/-15%), 50/60 Hz (± 10%).
Power Dissipation: 10W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing Total Connected Load: 15A Fast Blow, type SC or
equivalent.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to 140°F (-40°C to +60°C).
Storage: -40°F to 150°F (-40°C to +66°C).
Humidity: 85% relative humidity continuous, noncon-
densing.
Vibration: 0.5G environment.
Approvals:
Underwriters Laboratories Inc. Listed: File No. MP268.
ANSI/UL 60730-2-5 / CSA C22.2 No. 60730-2-5 -
Automatic Electrical Controls for Household and Simi-
lar Use, Part 2-5: Particular Requirements for Auto-
matic Electrical Burner Control Systems.
Factory Mutual Approved: Report No. J.I.1V9A0.AF.
Swiss RE (formerly IRI): Acceptable.
Federal Communications Commission, Part 15,
Class B—Emissions.
EAC: TC N RU д-US.Aи3O.B.04013
SIL 3 Capable:
SIL 3 Capable in a properly designed Safety Instru-
mented System. See form number 65-0312 for Cer-
tificate Agreement.

INSTALLATION

When Installing this Product...
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and
marked on the product to make sure the product is
suitable for the application.
3. Installer must be a trained, experienced, flame
safeguard service technician.
4. After installation is complete, check out the product
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property
damage.
Follow applicable safety requirements when
installing a control on a burner to prevent death or
severe injury.