Honeywell 7800 Series Installation Instructions Manual page 16

Valve proving primary relay modules
Hide thumbs Also See for 7800 Series:
Table of Contents

Advertisement

RM7898A 7800 SERIES VALVE PROVING PRIMARY RELAY MODULES
Edit:
-
Fig. 20. Confirm Correct screen.
19. Use the down arrow to confirm correct.
"Getting Data" will be displayed.
The following steps are used to confirm your selection.
Edit:
-
Fig. 21. Confirm Postpurge time.
20. Press Enter.
Edit:
-
Fig. 22. Confirm correct/incorrect screen.
21. Press Enter.
22. Press the down arrow to confirm the correct post-
purge time. "Getting Data" will be displayed until the
screen in Fig. 20 appears.
Edit:
-
Fig. 23. Setup Done screen.
23. Press and hold the relay module's RESET button for
five seconds to program the Valve Proving setup into
the relay module.
32-00209-03
+
M22671B
+
M22674A
+
M22671B
+
M22676B
The Release Reset screen will appear on the KDM.
Edit:
-
Fig. 24. Release Reset screen.
Future changes to the Valve Proving and PostPurge
features are still possible. With the relay module in
Standby, scroll to the Setup line and enter the password to
change the settings.
Once the system is in operation, the settings of the Valve
Proving and Postpurge can be viewed in Diagnostics,
using your S7800 Keyboard Module (KDM).
Select Mounting RM7898 Relay
Module
1. Mount the RM7898 vertically on the Q7800
Subbase, or mount horizontally with the knife blade
terminals pointing down. (For mounting on the
Q7800A, mount the RM7898 in an electrical
enclosure.)
2. When mounting in an electrical enclosure, provide
adequate clearance for service, installation and
removal of the RM7898, KDM, flame amplifier, flame
amplifier signal voltage probes, electrical signal
voltage probes, and electrical connections.
a. Allow an additional 2 in. (51 mm) below the
RM7898 for the flame amplifier mounting.
b. Allow an optional 3 in. (76 mm) minimum to both
sides of the RM7898 for electrical signal voltage
probes.
3. Make sure no subbase wiring is projecting beyond
the terminal blocks. Tuck in wiring against the back
of the subbase so it does not interfere with the knife
blade terminals or bifurcated contacts.
IMPORTANT
Install the RM7898 with a plug-in motion rather
than a hinge action.
4. Mount the RM7898 by aligning the four L-shaped
corner guides and knife blade terminals with the
bifurcated contacts on the wiring subbase and
securely tightening the two screws without
deforming the plastic.
Mounting Other System
Components (Fig. 24)
Mount other required and optional system components by
referring to Fig. 25 and the instructions provided with
each component.