Settings And Adjustments; Selectable Site-Configurable Jumpers - Honeywell 7800 Series Installation Instructions Manual

Valve proving primary relay modules
Hide thumbs Also See for 7800 Series:
Table of Contents

Advertisement

SEQUENCE
STATUS
LED PANEL
RESET
BUTTON
OPTIONAL
KEYBOARD
DISPLAY
MODULE
(STANDARD ON
RM7800G,L)
SETTINGS AND
ADJUSTMENTS
Selectable Site-Configurable
Jumpers
The relay module has three site-configurable jumper
options, see Fig. 25 and Table 8 on page 20. If necessary,
clip the site-configurable jumpers with side cutters and
remove the resistors from the relay module.
RM7898A 7800 SERIES VALVE PROVING PRIMARY RELAY MODULES
Q7800A1005
(plastic panel
mount version)
RUN/TEST
SWITCH
RELAY
MODULE
CONFIGURATION
JUMPERS
PURGE
TIMER
POWE R
PILOT
FLAM E
MAIN
ALARM
RESE T
SC RO LL
MO DE
- SA VE -
Fig. 25. Sequence Status LEDs.
SERVICE NOTE: Clipping and removing a site-
configurable jumper enhances the level of safety.
IMPORTANT
Clipping and removing a jumper after 200 hours of
operation causes a nonresettable Fault 110. The
relay module must then be replaced.
19
H O N E Y W E LL
CAPTIVE
MOUNTING
SCREW
FLAME
AMPLIFIER
M23166
32-00209—03

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents