A.1 Recommended Actions for Specific Code Occurrences
The Multinode Module contains a maximum of four nodes with each node occupying slots
which are numbered 1-2-3, 4-5-6, 7-8, or 9-10. Each node's processor (and its alphanumeric
display) is always located in slot 1 or 4 or 7 or 9.
To simplify the following explanation, slots are identified by a, b, or c which define the
1st, 2nd, or 3rd board in a given node regardless of its physical slot location.
Please note, when multiple recommendations are given for a window code-value, they are
organized in order from most to least likely.
Recommendations marked with * indicate an unimplemented code-value. Any such
occurrence should be brought to the attention of Honeywell TAC.
Window values marked as
replace K2LCN*
-
0
/ /
-
1
n
n=(-)
replace K2LCN; replace boards in slots b through c in turn
n=(1 thru 7) replace K2LCN
n=(other)
replace K2LCN*
-
2
n
n=(1 thru 7) replace board in slot b; replace K2LCN; replace the module backplane or
chassis assembly
n=(-) or (C) replace board in slot b; replace K2LCN; replace board in slot c if one
exists; replace the module backplane or chassis assembly
n=(other)
replace K2LCN*