How to Build a Title 24 Compliant System
California Title 24 Part 6 specifies mandatory requirements for en‐
closed parking garages. A compliant gas detection system can be con‐
structed from the Honeywell Analytics 301C24 and E³Point Network
gas sensor. This section describes how to configure the 301C control‐
ler to accomplish this.
Glossary
The terminology for a couple of technical concepts differs between
Honeywell and California.
California's
Honeywell's
Term
proximity
zone
alarm
Requirement: Section 120.6(c)4 "CO concentration at all sensors is
maintained at 25 ppm or less at all times."
Solution: Create an event for each group such that if one or more
sensors report a concentration greater than 25 ppm the event is acti‐
vated.
Term
A region of a garage containing several
sensors. Gas readings in the region are
group
presumed to be similar because of free
air circulation.
A notification from the gas detection
fault
system that the system is not working
correctly.
96
Description