Acqui Menu
4.
The Acquisition mode is accessible only when there is an SD card pre‐
sent (controllers with the Data Logging, or DLC function). It is used to
enable or disable the logging of system Events or transmitter infor‐
mation. The information is logged (or recorded) on an SD card. Inter‐
vals or conditions must be defined before using this option.
The first line of the Acquisition screen offers either:
First Line
Delay
Allows for delay intervals of 10 to 59 seconds or 1 to 60
mode
minutes.
Allows log values to be set according to set variation
Threshold
thresholds (based on last reading) of 3% or more, 5% or
mode
more or 10% or more of last detected concentration.
If a 3% threshold is selected, the system will not log a value at 3% but
will log a value of 3.1%. Remember that the sampling rate (system
refresh rate) may have an impact on logging.
Here is an example of threshold logging. The logs a semi‐colon delin‐
eated text files.
2005-04-27 11:05:20;1_CO2_ppm;574;-normal-:
2005-04-27 11:06:02;1_CO2_ppm;503;-normal-:
2005-04-27 11:06:15;1_CO2_ppm;562;-normal-:
2005-04-27 11:06:28;1_CO2_ppm;645;-normal-:
2005-04-27 11:06:39;1_CO2_ppm;557;-normal-:
2005-04-27 11:30:45;1_CO2_ppm;715;-normal-:
Description
50