ID50 Series Panel - Installation, Commissioning & Configuration Manual
CAUTION:
This product is not compliant
EN
EN
12094-1
12094-1
with EN 12094-1.
!
!
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.
3
1
997-263-000-11, Issue 11
January 2010
5.6.1.5 CBE Rules
The CBE Rules option is used during the SLC Loop
configuration. It is accessed through the Commissioning
Menu. The panel can be configured with up to 64 CBE rules.
This option enables modules to be assigned to a CBE Rule.
CLIP Loop Booster Support
The Loop Booster provides the additional power needed
by high-current-draw loop devices, such as loop sounders,
when the panel goes into alarm. When performing an SLC
Learn operation, all sounder modules are automatically
allocated for loop booster support. A '+' symbol, displayed
adjacent to the allocated CBE rule number, indicates that
the module will receive loop booster support (see below).
Note: if a device type is changed to one that may be loop
powered (i.e. SDR) to one that cannot (i.e. RLY),
either through manual type change or auto-learn
method, the loop-powered allocation is cleared.
Base Rule and Rule Range
Devices may be activated by any of up to 24 contiguously-
numbered CBE rules. When assigning modules to CBE rules
a Base Rule number has to be specified with an associated
rule range (up to 24 rules starting at the base rule) and the
auxiliary action. The Base Rule number and rule range apply
to AUX - Hold Switch, AUX - Abort Switch, SDR, SDH, CTL,
RLY, EST, MRL, IRL, ESO, ESE, RLE and CTE.
For input devices the range specifies which CBE rules
are affected by the input. The action taken by the CBE
rule depends on the type of input.
For outputs, the range specifies which CBE rules will affect
the output. The output takes the highest priority status from
a combination of all the CBE rules.
The Base Rule number has a valid range of 1-41 with a
default of 1. The Rule Range will default to having the first
CBE rule set only. To select or change the Rule number to
which a module is assigned:
[Module nn - SDR] 1 : Zone (nn)
3 : CBE Rule (nn+)
4 : [ Blank/Existing Text
1 With the module CBE Rules attributes screen
displayed, use the numeric keypad and press the '
button to select the CBE Rules option screen:
[Mnn] CBE Rules
01 -------------------------------------------- 24
1: Base [01 +: No ] NNNNNNNNNNNNNNNNNNNNNNNN
Note: Press the numeric
support '+' on or off.
2 Using the numeric keypad, press the
change the CBE Base Rule:
[Mnn] CBE Rules
01 -------------------------------------------- 24
Enter CBE Rule: _
3 Using the numeric keypad enter the desired Base Rule,
for example Rule 6, and press '
74
2 : Type
]
to toggle the Loop Booster
2
button to
1
< : Cancel
' to confirm. The
5
'
3