ID50 Series Panel - Installation, Commissioning & Configuration Manual
* Total system load is limited by the
transformer output
1
. The Notifier Loop
and Battery Calculator Support Tool,
should be used to ensure that the system
is NOT overloaded.
** Use the following loop driver source
impedance values for panel calculation
purposes: 3.8R at 22.5Vdc
997-263-000-11, Issue 11
January 2010
Volt-free Contact (VFC) Output Rating
Type:
Maximum load:
Fuse rating:
Switched -VE Output Rating
Output voltage:
Maximum load:
Loop Output
Output voltage:
Maximum load
1
:
Max. loop impedance**: 20 ohms (-ve cable only, with
Max. loop capacitance: 0.5μF
The panel (software version 5.04, or later) is compatible with
1
the Loop Booster Module (LBM). The LBM provides
additional power to the loop for output modules during panel
alarm conditions. Refer to the instructions (997-509-000-X)
provided with the LBM for a complete technical specification.
Up to 198 loop devices (up to 99 sensors and 99 modules) may
be fitted to the analogue loop.
The communication with devices on the loop can use either the
Notifier 'CLIP' or OPAL polling protocol. Refer to Hardware
Recommendations for a list of compatible devices and loading
limitations.
DC Auxiliary Rating
Output voltage range:
Maximum load:
Quiescent:
Alarm:
Fuse rating:
Note:
It is recommended that the auxiliary output
should not be used in the quiescent state other
than to provide a supply to drive ancillary devices'
power indicators.
RS485 Serial Port (Optional)
Isolation:
Baud rate:
Connector:
Maximum cable length: 1200metres (minimum of 1.5mm
A1 - 4
Single-pole change-over
Contacts rated 30V 1A
Not applicable
16 to 30V
83mA (total for both outputs)
22.5 to 26.4V.
0.5A peak current*
duplicate address detection) or 40
ohms (-ve cable only, without
duplicate address detection).
17.1 to 30V
250mA
150mA*
0.25A*
Cables should be capable of
carrying a minimum 1A.
Not applicable
Functional at 30V.
1200 Baud.
Terminal block on RS485 Interface
Module PCB.
screened cable recommended)