Honeywell Notifier ID50 Installation, Commissioning & Configuration Manual page 47

Hide thumbs Also See for Notifier ID50:
Table of Contents

Advertisement

ID50 Series Panel - Installation, Commissioning & Configuration Manual
6
EN54-4: 5.4
Mains fail delay
MUST not exceed 30
minutes.
1
or
2
8
6
1
3 Press the '
' button to toggle between 'On new zone
6
alarm' and 'On new point alarm' input options.
[Setup]
Un-mute = On new point alarm
> : Change
4 Press '
' to return to the Setup menu screen. All
4
changes will be saved on exiting.
5.5.1.7 Mains Fault Delay
By default, a mains fault is indicated within 10 seconds.
This option allows the delay to be extended up to 60
minutes in one minute increments. A fault indication
delay of more than 30 secs does not comply with
EN54 (see information at left). To configure a fault output
delay, proceed as follows:
1 From the Setup menu, using the numeric keypad press
the '
' button to enter the Panel Options menu.The
1
Language screen is displayed first.
[Setup] Language =
> : Change
2 Press the '
/
2
Options until the Mains Fault Delay screen is displayed.
[Setup]
Mains Fault Delay
> : Change
3 Press the '
' button to change the delay time to the
6
required setting:
[Setup]
Mains Fault Delay
Enter new value _
4 Use the numeric keypad to enter the new value:
[Setup]
Mains Fault Delay
> : Change
5 Press '
' to return to the Setup menu screen. All
4
changes will be saved on exiting.'
5.5.1.8 Diagnostic Mode
The Diagnostic Mode option allows extended fault and
fire reporting and determines whether events are
suppressed until confirmed. To enable Diagnostic Mode:
1 From the Setup menu, using the numeric keypad press
the '
' button to enter the Panel Options menu.The
1
Language screen is displayed first.
[Setup] Language =
> : Change
2 Press the '
/
2
Options until the Diagnostic Mode menu is displayed.
43
: More
< : Exit
English
: More
< : Exit
' buttons to step through the Panel
8
= 10
: More
< : Exit
= 10
: Confirm < : Cancel
= 20
: More
< : Exit
English
: More
< : Exit
' buttons to step through the Panel
8
997-263-000-11, Issue 11
January 2010