Honeywell Notifier ID50 Installation, Commissioning & Configuration Manual page 55

Hide thumbs Also See for Notifier ID50:
Table of Contents

Advertisement

ID50 Series Panel - Installation, Commissioning & Configuration Manual
CAUTION:
This product is not compliant
EN
EN
12094-1
12094-1
with EN 12094-1.
!
!
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.
3
or
2
8
4 Enter a delay time using the numeric buttons, between
0 and 999 secs, e.g. 90 secs:
[Setup]
Ext. System Soak =
Enter new value 90
Note: Entering a value of '0' means that the output, after
switching ON, is not switched OFF.
5 Press the '
Setup menu screen.
5.5.3.10 Hold Switch Operation
AUX modules, configured as one of four Hold Switch
categories, can be used to affect the Extinguishing
System Delay timer function. The four categories are:
AHJ - While this input is active, the Extinguishing System
Delay timer is reset to the configured value and paused.
NYC - While this input is active, the Extinguishing
System Delay timer is reset to the configured value
plus 90 secs and paused.
ULI - While active, the Extinguishing System Delay
timer continues to count down but pauses at 10 secs
before release.
IRI - Hold switch activity is ignored if two or more
zones associated with CBE rules with a category of
'Extinguishing System' are in alarm. Otherwise
operation is the same as type ULI.
Note: Only one of the above Hold Switch input types may
be used per panel.
1 From the Setup menu screen, press the '
the numeric keypad to enter the Device Options menu.
The Device blinking screen is displayed first.
[Setup]
> : Change
2 Press the '
6
Options until the LCD shows the Hold Switch
Operation menu.
[Setup]
> : Change
3 Press the '
NYC, ULI or IRI, as required. Changing the setting
saves the change automatically.
Note: The default selection is AHJ.
4 Press the '
Setup menu screen.
5.5.3.11 Transmission Device
The Transmission Device activates in response to an
alarm condition. The 'Transmission Device' menu enables
the configuration of either a continuous or a 6 second
51
0 Seconds
: Confirm
' button to confirm and return to the
5
Device Blinking = ON
: More
/
' buttons to step through the Device
2
8
Hold Switch Operation =
: More
' button to select alternative settings of
6
' button to confirm and return to the
5
997-263-000-11, Issue 11
< : Cancel
' button on
3
< : Exit
AHJ
< : Exit
January 2010