DISTRIBUTED I/O
Table 7. Relation between physical state and logical status as defined by the point attribute NO/NC for the XFL523B.
Contact Position
NO/NC Attribute
Open
NO
Closed
NO
Open
NC
Closed
NC
NV Name
nvoDiValue
nvoDiValueCnt
UCPTSensorConfig
UCPTSendOnDelta
SCPTDirection
EN0B-0090
Logical Status
0
1
1
0
Table 8. L
ON
Type
Range
SNVT_switch
SNVT_count
binary: 0, 1
totalizer: 0 to 65534
(65534 initial value)
0 (not used)
1 = binary (default)
2 = totalizer
SNVT_count
0 to 65535
SNVT_state
Input Voltage
≤ 2.5 V
≥ 5 V
≤ 2.5 V
≥ 5 V
M
Object NVs for the XFL523B.
ARK
Description
Transmits the state of the input channel every time
there is a state change or if SCPTMaxSendTime in
the Node Object has expired.
Transmits the state of the input channel every time
there is a state change or if SCPTMaxSendTime in
the Node Object is expired. If configured as a
totalizer, this NV transmits the number of transitions
from 0 to 1.
Specifies the setting for a sensor channel.
Specifies the difference in totalizer count required
before a transmission of the value output of the
Sensor Object takes place.
Used to define the relation between the logical status
of the input and the state of the LED. One bit cor-
responds to one input channel (bit 4 = input channel
12, bit 15 (MSB) = input channel 1). If a bit is clear,
the LED for the channel will be 0=green and 1=red. If
the bit is set, then 0=red and 1=green.
10
LED Switch On
LED Switch Off
Off
Green
Yellow
Red
Yellow
Red
Off
Green