Honeywell GENT VIG-LPC-EN Application

Honeywell GENT VIG-LPC-EN Application

Loop cards

Advertisement

Quick Links

Application
Loop Cards
(VIG-LPC-EN and COMPACT-LPC-EN)
The Loop Cards (VIG-LPC-EN and COMPACT-LPC-EN) are for use in Vigilon and Vigilon Compact panels. The Cards
can be identified by the
firmware version number label on the PCB, ensure the version requirements are met.
also be a
Selection
How to select a Loop card, MCC/MCB Card and PSU for
typical device mix found on sites:
a) Choose a selection method.
b) Use the information below to find a solution for a site.
1
Post March 2014
build of
EN Compact Loop card
(COMPACT-LPC-EN)
V4.48 or higher
2
Post March 2014
build of EN Vigilon
Loop card
(VIG-LPC-EN)
V4.48 or higher
Future scenario
A
B
2014
Up to 2Km loop
Up to 2Km loop
S4 range of products
Part 23 compliant
S4 with VAD
Pt23 compliant +
S4
S4 sensor sounders
and S4 sensors
S3 mark 1/2
S3 mark 3 VAD
Pt23 compliant
1
2
1
S4 Interfaces
VAD is a 'Visual Alarm Device' .
Typically the Compact panel based systems use devices shown in
T
A
B
s
site scenarios
,
and
Selection Method 1
a) Select a panel
b) Select applicable cards and PSU build
c) Determine which site device mix will work,
eg:
or
----
etc.
A
B
D
For example:
If we have an EN Vigilon 4/6 loop panel
(VIG-24) having Cards shown in
it will work with site device
mix
,
,
,
or
.
A
B
C
D
E
4188-1075 issue 3_Part 1_08/14
'SEC-GEN LOOP CARD' marking along the long edge on the component side of the PCB. There should
MCB
V4.52 or higher
A
will require
MCC
Post July 13
PSU
Pre or Post July 2013
Vigilon PSU
(VS-PSU-24) or
V4.52 or higher
(VS-PSU-72)
New scenario
Current scenario
C
Up to 1Km loop
S4 range of products
S4 range of products
S4
S3 mark 1/2
S4 Interfaces
2
1
2
Typical loop device mix found on sites
C
.
Selection Method 2
a) Select a site device mix, eg
b) Note the number in circle.
c) Match the number in circle with cards and
panels.
For example:
If a site has device mix
then
loop and you want to an EN Vigilon Compact
2
panel (COMPACT-24) then Cards
shown in
EN Vigilon 4/6 loop panel
(VIG1-24 or VIG1-72)
2
7
1
2
3
4
21 22 23 24
5
6
Zones
17 18 19 20
Fault
Healthy
Power Fault
Vigilon Fire System
System Fault
GENT 2012
Designed to EN54
Delay
Test
Previous
Disablement
B
or
A
B C D
E
D
Up to 1Km loop
34000 range of products
S3 mark 1
S4 Interfaces
34000
Interfaces
1
2
T
The Loop card (VIG-LPC-EN or COMPACT-LPC-EN) must never be
used in a Vigilon panel based System having device mix with
3
3400 sensors
A 1Km or 2km loop length is the sum the length of cable used on
the main loop and spur circuits off the main loop, on which
system devices are connected.
A
or
B
is installed on a 2Km
must be built into the panel
1
Vigilon Panels
EN Compact panel
(COMPACT-24)
1
14 15 16
8
9
10 11 12 13
29 30 30 32
25 26 27 28
Fire
15:45
Verify
Sounder
CB253
Pt 2 & 4
CB254
Power
Next
A
B C D
E
See note
Legacy secnarios
E
Up to 1Km loop
S4 and 34000 of products
S4
S3 mark 1/2
S4 Interfaces
1
2
2
5
6
F
.
Selection Method 3
B
D
----
etc.
a) Match the number in circle.
For example:
Panel
1
will work with
Cards
when used in site with
1
Device mix
F
Up to 1km loop
34000 and 3400 range
of products
34410
Fire Alarm Zone Module
3400
S3 mark 1
34000
Interfaces
.
1
1

Advertisement

loading

Summary of Contents for Honeywell GENT VIG-LPC-EN

  • Page 1 Application Loop Cards (VIG-LPC-EN and COMPACT-LPC-EN) The Loop Cards (VIG-LPC-EN and COMPACT-LPC-EN) are for use in Vigilon and Vigilon Compact panels. The Cards can be identified by the ‘SEC-GEN LOOP CARD’ marking along the long edge on the component side of the PCB. There should firmware version number label on the PCB, ensure the version requirements are met.
  • Page 2 Do not burn. accordance with national or local legislation. Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes.
  • Page 3 User guide Loop loading (VIG-LPC-EN and COMPACT-LPC-EN) This document shows how to determine the loop load and loop cable length for a Post March 2014 Loop Card fitted in a Vigilon panel: VIG-LPC-EN (for use in Vigilon 4-6 loop panels only) ...
  • Page 4 Loop Loading Loop Cable length The loop cable length is defi ned as the sum of the length of cable used on the main loop plus that used on all the spur circuits off the main loop having system devices. Loop device load and length calculations for 2Km loop card The loop device load can be up to 200 devices and the Loop Cable length can be up to 2Km when using Loop Card (VIG-LPC-EN or COMPACT-LPC-EN), where both device count and cable length are dictated by the number of alarm devices on the loop and...
  • Page 5 Loop Loading Maximum Alarm   No. of Alarm Device part limit current Devices current (mA) number Description per loop   on loop per device S4-711-VAD-LPW Dual Optical Heat & ______ x White VAD S4-711-VAD-HPR Dual Optical Heat & ______ x Red VAD ______ x...
  • Page 6 Loop Loading Maximum Alarm   No. of Alarm Device part limit current Devices current (mA) number Description per loop   on loop per device S2IP-ST-XR Strobe Red ______ x 4.00 S2IP-ST-XW Strobe White ______ x 10.0 S3-SN-X Sounder ______ x 2.00 S3IP-SN-X...
  • Page 7 Loop Loading Loop length and quantities for Standard mode with non VAD devices Use either Table 2 or Table 3 to determine the maximum number of devices on a loop and loop cable length possible for lumped alarm load. The examples 1 and 2 below show how to use the tables to determine loading and loop cable length. Table 2 Lumped load using 1.5mm²...
  • Page 8 Loop Loading Loop length and quantities for Enhance mode with VAD only devices Use either Table 4 or Table 5 to determine the maximum number of devices on a loop and loop cable length possible for lumped alarm load. The examples 1 and 2 below show how to use the tables to determine loading and loop cable length. Table 4 Lumped load using 1.5mm²...
  • Page 9 Loop Loading Panel messages associated with Loop cards V4.48 and possible actions Message.. Indications associated meaning.. possible action given.. with.. Loop n: High FAULT LED - On High resistance on 0v Use the Loop Diagnostic resistance on Buzzer - On (2Km Loop lines.
  • Page 10 Do not burn. accordance with national or local legislation. Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes.