Honeywell EXCEL 5000 OPEN SYSTEM XFL521B Product Data page 7

Distributed i/o, modules
Hide thumbs Also See for EXCEL 5000 OPEN SYSTEM XFL521B:

Advertisement

NV Name
Type
nviValue
SNVT_switch
nvoFeedback
SNVT_switch
UCPTSensorConfig
none
UCPTdriveTimeClose
SNVT_time_sec
UCPTdriveTimeOpen
SNVT_time_sec
SCPTdelayTime
SNVT_time_sec
SCPTminDeltaLevel
SNVT_lev_cont.
UCPTsyncMin
SNVT_lev_cont
UCPTsyncMin
SNVT_lev_cont
UCPTsyncCharge
SNVT_lev_cont
Table 6. L
M
Object NVs for the XFL522B.
ON
ARK
Range
0 = not used
6 = 0 to 10V (default)
7 = motor (floating)
10.0 to 1000s
(default = 90.0s)
10.0 to 1000s
(default = 90.0s)
0.0 to 10.0s
(default = 5.0s)
0 to10%
(default = 2%)
90 to 100%
(default = 98%)
0 to 127.5%
(default = 100%)
7
Description
Receives the value for the output channel.
Transmits the feedback value of the actuator output. If
the manual override switch is set to 0, or if the manual
override module is not plugged in, the feedback output
reflects the value of nviValue. As soon as the manual
override switch is set at the 20% threshold, the
Actuator Objects adopts this manual value. In this
case, the nvoFeedback state field will be 0xFF (invalid)
and the value field will contain the actuator position.
If the actuator is configured as a motor, the position
commanded with the manual override switch will be
reflected in the open/close commands for a floating
actuator.
If the manual override switch is in the automatic posi-
tion, data is transmitted whenever nviValue is written.
If the manual override switch is in the manual position,
data is transmitted whenever the manual position is
changed.
Specifies the actuator output type for an output
channel.
Specifies a floating actuator's runtime from 100% to
0%.
Specifies a floating actuator's runtime from 0% to
100%.
Specifies the delay time before a floating actuator
changes its direction. This avoids mechanical
problems that could occur when the run direction
changes due to an update to nviValue while the
actuator is still moving.
Specifies the delta level for an update to nviValue to
be exceeded before a new position is calculated for
the floating motor model. This is applicable only if the
actuator is configured as a motor.
Specifies the lower synchronization threshold. If the
actuator is configured as a motor and the value
commanded through nviValue approaches 0%, the
actuator is synchronized to 0% as soon as nviValue
reaches the percentage specified by UCPTsyncMin.
Specifies the upper synchronization threshold. If the
actuator is configured as a motor and the value
commanded through nviValue approaches 100%, the
actuator is synchronized to 100% as soon as nviValue
reaches the percentage specified by UCPTsyncMin.
Specifies the additional runtime when an actuator per-
forms a synchronization. This is to ensure that the
actuator reaches the end position even if the actuator
position is not what it should be due to inaccuracy.
For example, with UCPTsyncCharge at 100%, an
actuator with a theoretical current position of 20%
would be forced to run 120% of the runtime specified
by UCPTdriveTimeClose if it starts a synchronization
from this point of operation.
DISTRIBUTED I/O
EN0B-0090